7 hw counter, Hw counter, 6 configuration – JUMO 705010 mTRON T - Multichannel Controller Module Operating Manual User Manual
Page 66
6 Configuration
66
6.7
HW Counter
The controller module is equipped with a counter (hardware). Digital input 1 should be used as
a counter input (up to 10 kHz). The counter counts the rising edges of the input signal.
The counter reading and the switch-off signal (counter signal) are available in the analog se-
lector or digital selector.
Setup dialog
Parameters
"Counting" counter mode
The counter runs continuously. When it reaches the max. counter reading 65535 (0xFFFF), it
starts again at 0. (The switch-off signal is always 0.)
Parameter
Selection/settings
Description
Counter mode
Inactive
Counter is not active.
Counting
Counter is running continuously.
Charging
Counter is delivering switch-off signal.
Start signal
Digital selector (Inactive)
Signal (active for rising edge) to start the
counter (in "Charging" counter mode)
Threshold
Analog selector (Inactive)
Analog signal for specifying the switch-
off limit (in "Charging" counter mode)
Max. threshold
0 to 65535
Switch-off limit (in "Charging" counter
mode); active if no analog signal has
been selected (Threshold = Inactive).
Reset signal
Digital selector (Inactive)
Signal for resetting the counter
Inverting
Inversion of the reset signal
Inactive
Reset with high level (1)
Active
Reset with low level (0)
TAG number
7 characters
Identification marking (documentation in
PLC)
?