6 Configuration

86

Description of the function

Once the output level monitoring has been activated, determination of the mean output level
starts as soon as the actual value is within the control differential band. When the mean output
level has been determined, the current output level must be within the monitored output level
band. If it is not, an alarm is triggered.
In the event of a setpoint value change, the output level monitoring is temporarily deactivated
until the actual value returns to the control differential band. The mean output level is then de-
termined again.

Application examples:

Monitoring of signs of aging and faults on heating elements

Reporting of faults during operation

Functional limitations

Output level monitoring is not active in the following cases:

Proportional band Xp = 0

Self-optimization active

Manual mode

Ramp function active

Controller operating as program controller

Modulating controller without output level feedback (or output level feedback in "out of
range" state)

Position controller with output level feedback in "out of range" state

y

x

t

t

T

D

T

A

Dy

Dx

x Actual value

x Control differential band

y Output level

y Monitored output level band

T

D

Alarm delay

T

A

Alarm period