beautypg.com

13 digital outputs, Digital outputs, 6 configuration – JUMO 705010 mTRON T - Multichannel Controller Module Operating Manual User Manual

Page 104

background image

6 Configuration

104

6.13

Digital outputs

A maximum of eight digital outputs are available (output 3 to 10).

Setup dialog

Parameters

Contact type

This parameter can be used to invert the status. This function is available for all types of digital
output.

Status after change of configuration

Modified parameters are incorporated immediately.

Behavior after power on

During the initialization phase of the controller module, the output signal is inactive.

Parameter

Selection/settings

Description

Signal source

Digital selector (Inactive)

Signal that is issued via the digital out-
put.

Inactive = output inactive

Contact type

Switching behavior of digital output

Normally open contact (NO)

The output is active if the digital signal
(signal source) is active.

Normally closed contact (NC)

The output is inactive if the digital signal
(signal source) is active.

TAG number

7 characters

Identification marking (documentation in
PLC)

?

Type of digital output

"Active" status

"Inactive" status

Relay (N/O contact)

Closed

Open

Relay (changeover contact)

Operating position

Idle position

Logic output

High level (1)

Low level (0)

Solid state relay

Not inhibited

Inhibited

Open-collector output

Not inhibited

Inhibited