6 Configuration

82

Control loop monitoring

Control loop monitoring monitors the control behavior during startup of a plant and in the event
of a setpoint value step by analyzing the change of the actual value during an output level
change. An alarm is issued if the actual value does not respond according to the specifications.
The alarm signal is only available within the multichannel controller module in the digital selec-
tor (no transfer via system bus). It can, however, be selected as an input signal for the collective
alarm of the controller channel.

Setup dialog

Parameters

Parameter

Selection/settings

Description

Monitoring

Permitted

Control loop monitoring is generally per-
mitted

Not permitted

Control loop monitoring is not permitted

Response time

0 s to 9999 s

Time period in which the actual value
must leave the monitoring band.

"0 s" setting means:
Response time = reset time Tn

Monitoring band

0 to 1999

Range that the actual value must leave
within the response time.

"0" setting means:
Monitoring band = 0.5 × proportional
band (Xp)