11.1.3

Analog outputs

Per optional board (option slot 1 to 3)

Selectable output behavior in case of an error according to NAMUR recommendation NE 43
(for signal type 2 to 10 V and 4 to 20 mA).

11.1.4

Digital outputs

Standard version

1 analog output (configurable)

(Output 1 to 3)

Load resistance
R

Load

Accuracy

Ambient temperature
influence

Voltage DC 0(2) to 10 V

 500 

 0.25 %

 150 ppm/K

Current DC 0(4) to 20 mA

 500 

 0.25 %

 150 ppm/K

2 relay outputs (N/O)

Switching capacity

3A at AC 230V resistive load
3A at DC 30V resistive load

Contact life

150,000 operations at rated load / 350,000 operations at 1 A

or

2 logic outputs (to control external solid-state
relays)

Output signal

DC 0/15 V

Current

Max. 25 mA per output