6 Configuration

6.14

NV connecting list

The NV connecting list is used to link external inputs (NV_...) of the multichannel controller
module to signals from other modules via the system bus.
The following sections provide detailed lists of module signals:
Chapter 6.14.3 "Analog signals (overview)", page 108
Chapter 6.14.4 "Digital signals (overview)", page 110
Further information about the signals can be found in the operating manual for the relevant
module.
Replacement values are available in the event that these signals are not available (connection
to base unit interrupted in "Stop" state). The multichannel controller module uses replacement
values in normal operation and in independent mode.
Chapter 6.14.5 "Replacement values (overview)", page 115

Status after change of configuration

The connections are available immediately.

Behavior after power on

The connections are available immediately after system initialization.

TIP!
There is no NV connecting list in the input/output module configuration menu on the multi-
function panel. Instead, a central NV connecting list is available in the configuration menu of
the base unit (CPU).