6 Configuration

50

Digital inputs

If the HW counter is activated, the signal of digital input 1 is inactive.

Controller

(continued)

NV_C01TuneStart to
NV_C04TuneStart

External

Start self-optimization for control-
ler channel 1 to 4

NV_C01TuneStop to
NV_C04TuneStop

External

Abort self-optimization for control-
ler channel 1 to 4

NV_C01ParamSet to
NV_C04ParamSet

External

Changeover from parameter
block 1 to parameter block 2 for
controller channel 1 to 4

NV_C01ManualMode to
NV_C04ManualMode

External

Changeover to manual mode for
controller channel 1 to 4

NV_C01Stop to NV_C04Stop

External

Switch off controller channel 1 to
4

Setpoints

SP01RampTolBand to
SP04RampTolBand

Internal

Alarm signal of tolerance band
monitoring of ramp function 1 to 4

NV_SP01Changeover1 to
NV_SP04Changeover1

External

Bit 0 of setpoint changeover of
setpoint value function 1 to 4

NV_SP01Changeover2 to
NV_SP04Changeover2

External

Bit 1 of setpoint changeover of
setpoint value function 1 to 4

Analog inputs

AI01Alarm1 to AI04Alarm1

Internal

Alarm signal 1 of analog input 1 to
4

AI01Alarm2 to AI04Alarm2

Internal

Alarm signal 2 of analog input 1 to
4

Digital inputs

DI01, DI02, DI05 to DI10

Internal

Signal of digital input 1, 2, 5 to 10

NVDigitalOutputs NV_DO03 to NV_DO10

External

Signal for controlling digital output
3 to 10

Limit monitoring

LI01 to LI04

Internal

Output signal of limit value moni-
toring 1 to 4

NV_LI01Confirmation to
NV_LI04Confirmation

External

Signal to acknowledge the output
signal of limit value monitoring 1
to 4

Mathematics

Logic01 to Logic04

Internal

Result of logic function 1 to 4

Signal rejections

NV_SR01 to NV_SR08

External

Signal for activating signal sup-
pression of digital input 1, 2, 5 to
10

Alarm

CollectiveAlarm

Internal

Controller module collective alarm

HW counter

HWCounterSignal

Internal

Signal of hardware counter in "fill"
operating mode (as switch-off sig-
nal when threshold value
reached)

Digital links

DigitalLink01 to DigitalLink04

Internal

Result of binary linking 1 to 4

Category

Signal

Type

Description

?

?