11 Appendix
Standard signals
Measuring circuit monitoring
In the event of an error the outputs move to a defined status.
11.1.2
Digital inputs
Designation
Measuring range
Measuring accu-
racy
1
Ambient tempera-
ture influence
Voltage
0.05 %
100 ppm/K
Input resistance R
E
> 500 k
DC 0(2) to 10 V
Input resistance R
E
> 100 k
DC 0 to 1 V
Current (voltage drop
2 V)
DC 0(4) to 20 mA
0.05 %
100 ppm/K
Heater current
AC 0 to 50 mA
1 %
100 ppm/K
Resistance transmitter
100
to 4 k
4
100 ppm/K
Resistance/potentiometer
100
to 4 k
4
100 ppm/K
1
The accuracy values refer to the maximum measuring range. Smaller measuring ranges lead to reduced lineariza-
tion accuracy.
Measuring element
Underrange
Overrange
Probe or lead
short circuit
Probe or lead
break
Thermocouple
Is detected
Is detected
Is not detected
Is detected
RTD temperature probe
Is detected
Is detected
Is detected
Is detected
Voltage
2 to 10 V
Is detected
Is detected
Is detected
Is detected
0 to 10 V
Is detected
Is detected
Is not detected
Is not detected
0 to 1 V
Is detected
Is detected
Is not detected
Is not detected
Current
4 to 20 mA
Is detected
Is detected
Is detected
Is detected
0 to 20 mA
Is not detected
Is detected
Is not detected
Is not detected
Heater current
Is detected
Is detected
Is not detected
Is not detected
Resistance transmitter
Is detected
Is detected
Is not detected
Is detected
Resistance/potentiometer
Is detected
Is detected
Is detected
Is detected
Number (standard version)
2 (input 1 and 2)
Optional number (option slot 1 to 3)
6 (input 5 to 10)
Input signal
DC 0/24 V (Input 1: Counting input up to 10 kHz)
(PLC level; logical "0” = -3 to +5 V; logical "1” = +15 to +30 V)