2 digital inputs, 11 appendix – JUMO 705010 mTRON T - Multichannel Controller Module Operating Manual User Manual

Page 143

background image

143

11 Appendix

Standard signals

Measuring circuit monitoring

In the event of an error the outputs move to a defined status.

11.1.2

Digital inputs

Designation

Measuring range

Measuring accu-
racy

1

Ambient tempera-
ture influence

Voltage

 0.05 %

100 ppm/K

Input resistance R

E

> 500 k

DC 0(2) to 10 V

Input resistance R

E

> 100 k

DC 0 to 1 V

Current (voltage drop

 2 V)

DC 0(4) to 20 mA

 0.05 %

100 ppm/K

Heater current

AC 0 to 50 mA

 1 %

100 ppm/K

Resistance transmitter

100

 to 4 k

 4 

100 ppm/K

Resistance/potentiometer

100

 to 4 k

 4 

100 ppm/K

1

The accuracy values refer to the maximum measuring range. Smaller measuring ranges lead to reduced lineariza-
tion accuracy.

Measuring element

Underrange

Overrange

Probe or lead
short circuit

Probe or lead
break

Thermocouple

Is detected

Is detected

Is not detected

Is detected

RTD temperature probe

Is detected

Is detected

Is detected

Is detected

Voltage

2 to 10 V

Is detected

Is detected

Is detected

Is detected

0 to 10 V

Is detected

Is detected

Is not detected

Is not detected

0 to 1 V

Is detected

Is detected

Is not detected

Is not detected

Current

4 to 20 mA

Is detected

Is detected

Is detected

Is detected

0 to 20 mA

Is not detected

Is detected

Is not detected

Is not detected

Heater current

Is detected

Is detected

Is not detected

Is not detected

Resistance transmitter

Is detected

Is detected

Is not detected

Is detected

Resistance/potentiometer

Is detected

Is detected

Is detected

Is detected

Number (standard version)

2 (input 1 and 2)

Optional number (option slot 1 to 3)

6 (input 5 to 10)

Input signal

DC 0/24 V (Input 1: Counting input up to 10 kHz)
(PLC level; logical "0” = -3 to +5 V; logical "1” = +15 to +30 V)