6 Configuration

Alarm function

For alarm function AF1 to AF6, the resulting limit value depends on the setpoint value – the
entered limit value is added to the setpoint value or subtracted from the setpoint value. Alarm
functions AF7 and AF8 work with a fixed limit value that corresponds to the entered limit value.
Chapter 6.11.2 "Alarm and hysteresis functions", page 100

Acknowledge-
ment

Condition for acknowledgement of the output signal (self-maintaining)

OFF

No acknowledgement required (output
signal is deactivated automatically if the
alarm condition is no longer present).

If inactive

Acknowledgement only possible if alarm
condition is no longer present.

Always

Acknowledgement is always possible.

Acknowledg. sig-
nal

Digital selector (Inactive)

Signal (high-active) for acknowledging
the output signal

Limit value

-99999 to 0 to +99999

Admissible deviation of the actual value

Switching differ-
ential

0 to 1 to 99999

Switching thresholds of the output signal
(difference from limit value)

Hysteresis func-
tion

Switching differential position around the limit value

Symmetric

Switching differential is positioned with
half above and half below the limit value.

Asymmetric left

Switching differential is below the limit
value (typically).

Asymmetric right

Switching differential is above the limit
value (typically).

Start-up
alarm suppres-
sion

Alarm suppression during start-up phase

Inactive

Limit value monitoring always operates
according to its alarm function.

Active

No alarm after power on or if limit value
or setpoint value is changed

Switch-on delay

0 to 65535 s

Delay time for activation of the output
signal if alarm condition is present.

Switch-off delay

0 to 65535 s

Delay time for deactivation of the output
signal if alarm condition is no longer
present.

Pulse time

0 to 65535 s

Output signal is deactivated automati-
cally after this time.

Signal at O-o-R

Output signal in the event of deviation above or below the measuring range

OFF

Output signal inactive

ON

Output signal active

Parameter

Selection/settings

Description

?

?