6 Configuration
Alarm function
For alarm function AF1 to AF6, the resulting limit value depends on the setpoint value – the
entered limit value is added to the setpoint value or subtracted from the setpoint value. Alarm
functions AF7 and AF8 work with a fixed limit value that corresponds to the entered limit value.
Chapter 6.11.2 "Alarm and hysteresis functions", page 100
Acknowledge-
ment
Condition for acknowledgement of the output signal (self-maintaining)
OFF
No acknowledgement required (output
signal is deactivated automatically if the
alarm condition is no longer present).
If inactive
Acknowledgement only possible if alarm
condition is no longer present.
Always
Acknowledgement is always possible.
Acknowledg. sig-
nal
Digital selector (Inactive)
Signal (high-active) for acknowledging
the output signal
Limit value
-99999 to 0 to +99999
Admissible deviation of the actual value
Switching differ-
ential
0 to 1 to 99999
Switching thresholds of the output signal
(difference from limit value)
Hysteresis func-
tion
Switching differential position around the limit value
Symmetric
Switching differential is positioned with
half above and half below the limit value.
Asymmetric left
Switching differential is below the limit
value (typically).
Asymmetric right
Switching differential is above the limit
value (typically).
Start-up
alarm suppres-
sion
Alarm suppression during start-up phase
Inactive
Limit value monitoring always operates
according to its alarm function.
Active
No alarm after power on or if limit value
or setpoint value is changed
Switch-on delay
0 to 65535 s
Delay time for activation of the output
signal if alarm condition is present.
Switch-off delay
0 to 65535 s
Delay time for deactivation of the output
signal if alarm condition is no longer
present.
Pulse time
0 to 65535 s
Output signal is deactivated automati-
cally after this time.
Signal at O-o-R
Output signal in the event of deviation above or below the measuring range
OFF
Output signal inactive
ON
Output signal active
Parameter
Selection/settings
Description
?
?