7 Parameterization

118

Reset time 1

(Tn1)

0 to 350 to 9999 s

The reset time influences the integral
component (I component) of the control-
ler output signal.

The greater the reset time, the less
effect the I component has.

Reset time 2

(Tn2)

0 to 350 to 9999 s

Switching period
1

(Cy1)

0 to 20 to 999.9 s

When using a switched output, the cycle
time should be chosen so that the
energy supply to the process is as con-
tinuous as possible without overloading
the switching elements.

Switching period
2

(Cy2)

0 to 20 to 999.9 s

Contact spacing

(Xsh)

0 to 999.9

Spacing between the two control con-
tacts for a three-state controller, modu-
lating controller, and continuous
controller with integrated position con-
troller

Switch. differen-
tial 1

(Xd1)

0 to 1 to 999.9

Hysteresis for a switching controller with
proportion band Xp = 0

Switch. differen-
tial 2

(Xd2)

0 to 1 to 999.9

Actuator time

(TT)

5 to 60 to 3000 s

Control valve running time range used
for a modulating controller and continu-
ous controller with integrated position
controller

Working point

(Y0)

-100 to 0 to +100 %

Working point correction for a P or PD
controller (correction value for the output
level)

If the actual value (x) has reached the
setpoint value (w), the output level (y)
corresponds to the working point (Y0).

Max. outp. level
limit.

(Y1)

0 to 100 %

Admissible maximum output level (only
effective if Xp

 0)

Min. outp. level
limit.

(Y2)

-100 to +100 %

Admissible minimum output level (only
effective if Xp

 0)

Relay ON period
1

(Tk1)

0 to 60 s

Limits the frequency of switching for
switched outputs

Relay ON period
2

(Tk2)

0 to 60 s

Parameter

Setting

Description