6 Configuration

102

6.12

Analog outputs

A maximum of three analog outputs can be configured as current or voltage outputs (standard
signal) and are freely scalable.

Setup dialog

Parameters

Parameter

Selection/settings

Description

Signal source

Analog selector (Inactive)

Analog signal that is issued via the ana-
log output.

If "Inactive" is selected, no signal is
issued.

Signal type

Physical output signal

0 ... 10 V

Standard signal for voltage

2 ... 10 V

Standard signal for voltage

0 ... 20 mA

Standard signal for current

4 ... 20 mA

Standard signal for current

Behavior on error Value of the output signal after deviation above or below the measuring range (out

of range = O-o-R)

The options "NAMUR Low" and "NAMUR High" are only available for signal types
2 ... 10 V and 4 ... 20 mA.

NAMUR Low

Value for deviation below measured
value/short-circuit according to NAMUR
recommendation

NAMUR High

Value for deviation above measured
value/probe break according to NAMUR
recommendation

Signal at O-o-R

Adjustable value (see "Signal at O-o-R"
parameter)

Last value

The last value is retained.

?