6 Configuration
Setpoint
This value is used as a fixed setpoint value if no external setpoint value has been selected (In-
active). Otherwise, this value is used as a correction value (offset, negative or positive) for the
external setpoint value.
If a setpoint value has already been specified using the multifunction panel, it is displayed here
and can be changed if necessary.
Setpoint changeover
6.10.1
Ramp function
The ramp function enables a steady change of the setpoint value up to the ramp end value (ac-
tive setpoint value). The ramp start value is specified with an analog signal (e.g. current actual
value) or with a fixed start value.
A tolerance band can be set around the setpoint value line to monitor the actual value. If the
actual value deviates from the tolerance band, a digital signal (tolerance band signal) is acti-
vated.
Setpoint 1
-99999 to 0 to +99999
Fixed setpoint 1 or correction value
External
setpoint 2
Analog selector (Inactive)
Analog signal as setpoint 2
Setpoint 2
-99999 to 0 to +99999
Fixed setpoint 2 or correction value
External
setpoint 3
Analog selector (Inactive)
Analog signal as setpoint 3
Setpoint 3
-99999 to 0 to +99999
Fixed setpoint 3 or correction value
External
setpoint 4
Analog selector (Inactive)
Analog signal as setpoint 4
Setpoint 4
-99999 to 0 to +99999
Fixed setpoint 4 or correction value
Setp. change-
over 1
Digital selector (Inactive)
Binary value (bit 0) for controlling set-
point changeover
Setp. change-
over 2
Digital selector (Inactive)
Binary value (bit 1) for controlling set-
point changeover
Start limit
-99999 to +99999
Minimum admissible setpoint value
End limit
-99999 to +99999
Maximum admissible setpoint value
Parameter
Selection/settings
Description
?
?
?
Setpoint changeover 2 (bit 1)
Setpoint changeover 1 (bit 0)
Active setpoint value
0
0
1
0
1
2
1
0
3
1
1
4