6 configuration – JUMO 705010 mTRON T - Multichannel Controller Module Operating Manual User Manual

Page 57

background image

57

6 Configuration

Measuring range
start

Factory setting depends on sensor and linearization.

-99999 to +99999

Start value of the measuring range (for
resistance transmitter, standard signal,
and potentiometer) to detect out of
range

Measuring range
end

Factory setting depends on sensor and linearization.

-99999 to +99999

End value of measuring range (see
above) to detect out of range

Scale start

Factory setting depends on sensor and linearization.

-99999 to +99999

Start value of display range

Scale end

Factory setting depends on sensor and linearization.

-99999 to +99999

End value of display range

TAG number

7 characters

Identification marking (documentation in
PLC)

Unit

5 characters (%)

Unit for numerical representation of
measured value

Offset type

Type of measured value offset

Standardized

Offset of standardized measured value
(after linearization)

Physical

Offset of physical measured value
(before linearization)

Offset

-100 to 0 to +100

Correction value

Filter time con-
stant

0 s to 0.6 s to 100 s

Time constant for adjusting the digital
input filter (0 s = filter off)

Cold junction

Selection of cold junction (for thermocouple)

Internal Pt100

Internal Pt100 temperature probe

External constant

Constant cold junction temperature

Ext. reference
temp.

-20 to 0 to +200

Cold junction temperatures (for thermo-
couple and constant cold junction tem-
perature)

Resistance Ra or
Ro

0

 to 4000 

For Resistance transmitter:
Resistance Ra between sliding contact
(S) and start (A), if the sliding contact is
positioned at the start.

For Resistance/potentiometer:
Offset resistance Ro

Resistance Rs or
Rx

6

 to 1000  to 4000 

For Resistance transmitter:
Resistance range Rs of sliding contact

For Resistance/potentiometer:
Shifting resistance range Rx

Parameter

Selection/settings

Description

?

?

?

?

?

?

?

?

?