6 configuration – JUMO 705010 mTRON T - Multichannel Controller Module Operating Manual User Manual
Page 57
57
6 Configuration
Measuring range
start
Factory setting depends on sensor and linearization.
-99999 to +99999
Start value of the measuring range (for
resistance transmitter, standard signal,
and potentiometer) to detect out of
range
Measuring range
end
Factory setting depends on sensor and linearization.
-99999 to +99999
End value of measuring range (see
above) to detect out of range
Scale start
Factory setting depends on sensor and linearization.
-99999 to +99999
Start value of display range
Scale end
Factory setting depends on sensor and linearization.
-99999 to +99999
End value of display range
TAG number
7 characters
Identification marking (documentation in
PLC)
Unit
5 characters (%)
Unit for numerical representation of
measured value
Offset type
Type of measured value offset
Standardized
Offset of standardized measured value
(after linearization)
Physical
Offset of physical measured value
(before linearization)
Offset
-100 to 0 to +100
Correction value
Filter time con-
stant
0 s to 0.6 s to 100 s
Time constant for adjusting the digital
input filter (0 s = filter off)
Cold junction
Selection of cold junction (for thermocouple)
Internal Pt100
Internal Pt100 temperature probe
External constant
Constant cold junction temperature
Ext. reference
temp.
-20 to 0 to +200
Cold junction temperatures (for thermo-
couple and constant cold junction tem-
perature)
Resistance Ra or
Ro
0
to 4000
For Resistance transmitter:
Resistance Ra between sliding contact
(S) and start (A), if the sliding contact is
positioned at the start.
For Resistance/potentiometer:
Offset resistance Ro
Resistance Rs or
Rx
6
to 1000 to 4000
For Resistance transmitter:
Resistance range Rs of sliding contact
For Resistance/potentiometer:
Shifting resistance range Rx
Parameter
Selection/settings
Description
?
?
?
?
?
?
?
?
?