beautypg.com

11 appendix, 1 technical data, 1 analog inputs – JUMO 705010 mTRON T - Multichannel Controller Module Operating Manual User Manual

Page 141: Appendix, Technical data

background image

141

11 Appendix

11.1

Technical data

11.1.1

Analog inputs

General information

Thermocouples

RTD temperature probe

Number (standard version)

2 (input 1 and 2)

Optional number (option slot 1 to 3)

2 (input 3 and 4)

A/D converter

Dynamic resolution up to 16 bit

Designation

Standard

Measuring range

Measuring accu-
racy

1

Ambient tempera-
ture influence

Fe-CuNi “L”

-200 to +900 °C

 0.1 % from -100 °C 300 ppm/K

Fe-CuNi “J”

DIN EN 60584

-200 to +1200 °C

 0.1 % from -100 °C 300 ppm/K

Cu-CuNi “U”

-200 to +600 °C

 0.1 % from -130 °C 300 ppm/K

Cu-CuNi “T”

DIN EN 60584

-200 to +400 °C

 0.1 % from -150 °C 300 ppm/K

NiCr-Ni “K”

DIN EN 60584

-200 to +1372 °C

 0.1 % from -80 °C

300 ppm/K

NiCr-CuNi “E”

DIN EN 60584

-200 to +1000 °C

 0.1 % from -80 °C

300 ppm/K

NiCrSi-NiSi “N”

DIN EN 60584

-100 to +1300 °C

 0.1 % from -80 °C

300 ppm/K

Pt10Rh-Pt “S”

DIN EN 60584

-50 to 1768 °C

 0.15 % from 20 °C 300 ppm/K

Pt13Rh-Pt “R”

DIN EN 60584

-50 to 1768 °C

 0.15 % from 20 °C 300 ppm/K

Pt30Rh-Pt6Rh “B”

DIN EN 60584

0 to 1820 °C

 0.15 % from 400 °C 300 ppm/K

W5Re-W26Re “C”

0 to 2320 °C

 0.15 % from 500 °C 300 ppm/K

W3Re-W25Re “D”

0 to 2495 °C

 0.15 % from 500 °C 300 ppm/K

W3Re-W26Re

0 to 2400 °C

 0.15 % from 500 °C 300 ppm/K

Chromel-Copel

GOST 8.585-
2001

-200 to +800 °C

 0.15 % from -80 °C 300 ppm/K

Chromel-Alumel

GOST 8.585-
2001

-200 to +1372 °C

 0.1 % from -80 °C

300 ppm/K

PLII (Platinel II)

0 to 1395 °C

 0.1 % from -80 °C

300 ppm/K

Linear

0 to 75 mV

 0.1 %

300 ppm/K

Cold junction

Pt100 internal

Cold junction accuracy

 1 K

1

The accuracy values refer to the maximum measuring range. Smaller measuring ranges lead to reduced lineariza-
tion accuracy.

Designation

Standard

Measuring range

Measuring accu-
racy

1

Ambient tempera-
ture influence

Pt100

DIN EN 60751

-200 to +850 °C

50 ppm/K

2-wire circuit

 0.15 %

3-wire/4-wire circuit

 0.05 %

Pt500

DIN EN 60751

-200 to +850 °C

50 ppm/K

2-wire circuit

 0.30 %

3-wire/4-wire circuit

 0.15 %