6 Configuration

Resistance Ra or Ro, Rs or Rx, Re

The overall resistance Ra + Rs + Re (or Ro + Rx) must not exceed 4000

.

Status after change of configuration

The input values before the change of configuration are not saved; the new input values are
available approx. 2 seconds after the change of configuration.

Behavior after power on

All analog inputs are initialized and start their measurements over (no statuses are saved with
power off).

Error processing

The behavior in the event of deviation above or below the measuring range (out of range) can
be configured. The settings should be made in:

Controller configuration

Limit value monitoring

Analog outputs

The settings made there also apply for probe/conductor breaks or probe/conductor short-cir-
cuits. This produces a safe state for operation in the event of an error.
Error detection depends on the type of measuring probe (see technical data, measuring circuit
monitoring).

Resistance transmitter

Resistance/potentiometer in 2-wire circuit

Resistance/potentiometer in 3-wire circuit

Resistance/potentiometer in 4-wire circuit

Re

Rs

Ra

E

S

A

Rx

Ro

Ro

Rx

Ro

Rx