JUMO 706560 LOGOSCREEN es Data Sheet User Manual
Block structure, Key features, Approvals
Page 1/12
JUMO GmbH & Co. KG
Delivery address:Mackenrodtstraße 14,
36039 Fulda, Germany
Postal address: 36035 Fulda, Germany
Phone:
+49 661 6003-0
Fax:
+49 661 6003-607
e-mail:
Internet:
www.jumo.net
JUMO Instrument Co. Ltd.
JUMO House
Temple Bank, Riverway
Harlow, Essex CM20 2DY, UK
Phone: +44 1279 635533
Fax:
+44 1279 635262
e-mail:
Internet: www.jumo.co.uk
JUMO Process Control, Inc.
8 Technology Boulevard
Canastota, NY 13032, USA
Phone:
315-697-JUMO
1-800-554-JUMO
Fax:
315-697-5867
e-mail:
Internet: www.jumo.us
Data Sheet 70.6560
2009-12-14/00415638
Block structure
STN color screen
320 x 240 pixels, 27 colors
CPU board
Internal
memory,
256 MByte
Main
memory
SRAM
Setup
interface
Interface for
measurement and
configuration data
Slot II
Slot I
Analog input board 1
7 binary inputs
110 — 240 V AC
+10/-15%, 48 — 63 Hz
30 V AC/DC
48 — 63 Hz
or 20 —
,
6 inputs,
electrically isolated
through optocouplers
6 inputs,
electrically isolated
through optocouplers
Interface for
measurement and
configuration data
RS232 or RS422/485 interface
Ethernet interface
CompactFlash memory card
256 MByte
4 relays (make/
break), 1 open-
collector output
(make/break),
voltage output
24 V/ 50 mA
1 relay (changeover)
I/O board
PSU board
CompactFlash
memory card for
measurement and
configuration data
LON interface
PROFIBUS-DP interface
Interface for
measurement data
Analog input board 1
Key features
k conforms to FDA CFR Part 11
k monitored back-panel cover
k no chart /pens
k presentation of the measurement
data in vertical/horizontal diagrams,
bar graph, numerical, …
k batch reporting
k local availability of the measurement
data stored in RAM
k data records can be saved to a
CompactFlash memory card
k instrument can be configured from the
keypad, via the CompactFlash memory
card or serial interface
k evaluation of the archived data
through the PC evaluation software
k adaptation of the storage cycles to the
individual process through
- normal operation
- event operation
- day-time operation
k report with minimum/maximum/
average values and integrator
k freely programmable inputs for
resistance thermometers,
thermocouples, DC current and
DC voltage
k sampling cycle minimum 125msec
with 12 analog inputs
k PROFIBUS-DP and Ethernet connection
k integrated web server
Approvals
Paperless Recorder for secure
acquisition of FDA-compliant
measurement data
Brief description
Together with its PC software components, this paperless recorder provides a closed sys-
tem for the electronic acquisition, storage and archiving of process data that fulfills the re-
quirements of FDA 21 CFR Part 11.
The presentation is mainly determined by a 5.7" color screen, on which the measurement
data are displayed in different formats (numbers, diagrams, bar graph...).
The integrated Security Manager ensures that only authorized persons can operate the in-
strument, and the integrated Audit-Trail Manager ensures seamless documentation of all
operative actions.
Measurement data are electronically stored and available for evaluation both locally and
on a PC. Front bezel size is 144 mm x 200 mm, maximum mounting depth is 228 mm.
es
Type 706560/ …
Type 706560/…, stainless steel front