6 Configuration

78

Optimization according to the step response method

Initially, a configurable standby output is produced until the actual value "settles" to a constant.
This is automatically followed by a configurable output level step (step size) to the control path.
Main applications of the step response method:

Optimization immediately after "power on" during startup (considerable time saving, stand-
by output setting = 0 %)

Control path does not oscillate easily (e.g. extremely well insulated furnace with low losses,
long oscillation period)

Actual value must not exceed the setpoint value
If the output level is known for the corrected setpoint value, overshooting is prevented with
the following setting:
Standby output + step size

 output level in corrected state

The progression of the output level and actual value depends of the status of the process at
the point when self-optimization starts:

Self-optimization during the startup
phase

Self-optimization during operation

t

y

S

y

t

x

w

t1 t2

t3

}

Dy

{

y

x

y

S

t1

t2

t3

Dy

t

t

w

y Output level

y Step size

y

S

Standby output

t1 Start of self-optimization

x Actual value

t2 Point of output level step

w Setpoint value

t3 End of self-optimization