6 Configuration

Status after change of configuration

The output signal to the system bus always adopts the status that corresponds to the current
configuration.

Behavior after power on

After initialization, the input signals are available immediately, according to their configuration.

6.6.1

Alarm

Signal monitoring can be activated for each digital input.

Setup dialog

Parameters

Event text

Setup program: Selection of text from a list
Click the "..." button to open a list with the text numbers and the associated texts. The texts can
be edited.
Multifunction panel: Selection of text using the text number
The setup program is required to view and edit the texts.

Parameter

Selection/settings

Description

Alarm type

The alarm type is not set by default.

Collective alarm

Alarm results in collective alarm of con-
troller module.

Event

Alarm results in an entry (event text) in
the event list.

Alarm at level

High (1)

Alarm at high level (1)

Low (0)

Alarm at low level (0)

Event text

Use default text or select other text from
the list.

Text that is entered in the event list for
an alarm (if Alarm type = "Event").

?