6 configuration, 1 analog selector, Configuration – JUMO 705010 mTRON T - Multichannel Controller Module Operating Manual User Manual
Page 47: Analog selector
47
6 Configuration
6.1
Analog selector
The analog selector contains all analog signals that are available in the multichannel controller
module for configuration.
The following table lists all analog signals. The entry in the "Type" column indicates the source
of the signal:
•
Internal only: Internal signal that is only available inside the multichannel controller module.
•
Internal: Internal signal of the multichannel controller module (including signals of analog
inputs)
The signal is also transmitted to the base unit via the system bus, to allow it to be used by
other modules.
•
External: External input (NV_...) that must be linked in the NV connecting list to a signal
from another module (see Chapter 6.14 "NV connecting list", page 105).
The signal name "NV_..." indicates the intended use; in principle, the signal can also be
used for other purposes.
TIP!
The parameters described in this section can be configured either with the setup program or
with the multifunction panel (exception: Device data and replacement values).
Category
Signal
Type
Description
Inactive
No signal selected
Further signals
SamplingRate
Internal
only
Sampling rate of controller
module
Controller
NV_C01ActualValue to
NV_C04ActualValue
External
Actual value for controller channel
1 to 4
NV_C01Setpoint to
NV_C04Setpointt
External
Setpoint value for controller chan-
nel 1 to 4
C01OutpLevelMon to
C04OutpLevelMon
Internal
Output level (display value) of
controller channel 1 to 4
C01OutpLevel1 to
C04OutpLevel1
Internal
Output level at first controller out-
put (continuous) of controller
channel 1 to 4
C01OutpLevel2 to
C04OutpLevel2
Internal
Output level on second controller
output (continuous) of controller
channel 1 to 4
C01Diff to C04Diff
Internal
Difference between setpoint value
and actual value of controller
channel 1 to 4