8 configuration – in setup program only, 1 customer-specific linearization, Configuration – in setup program only – JUMO 705010 mTRON T - Multichannel Controller Module Operating Manual User Manual
Page 121: Customer-specific linearization
121
8 Configuration – in setup program only
8.1
Customer-specific linearization
You can use the customer-specific linearization to create a customized linearization character-
istic line for analog inputs. This characteristic line is used for all analog inputs for which the cor-
responding linearization has been selected in the configuration.
Customer-specific linearization can only be programmed with the setup program. Two proce-
dures are available for this (type of linearization: grid points or formula).
Signal flow
TIP!
The parameters described in this section can only be configured with the setup program.
TIP!
It is possible to create different characteristic lines with grid points and formulae. The decisive
factor for use in the module is, however, the characteristic line to which the formula corre-
sponds. If when you use "OK" to exit the dialog, the grid points and formulae are not compat-
ible, you are given a warning. You can delete the grid points or recalculate the formula on the
basis of the grid points.
<<<<
>>>>
y
x
<<<<
>>>>
+
+
(1)
(2)
(3)
(4)
(5)
(6)
(7)
(1) Measured value
(5) Offset (standardized)
(2) Offset (physical)
(6) Linearized value monitoring with respect to
the scale (configuration parameter: Scale
start, Scale end)
(3) Measured value monitoring of standard sig-
nals (limits acc. to NAMUR)
(7) Linearized value
(4) Linearization (grid points / formula)
Grid points: Domain monitoring (measured
values)
Formula: Co-domain monitoring (linearized
values) with respect to the measuring range
(configuration parameter: Measuring range
start, Measuring range end)