6 Configuration

96

6.11

Limit value monitoring

One of eight alarm functions can be selected for each of the four instances of limit value mon-
itoring in order to monitor a chosen input value (actual value) in relation to a fixed limit value or
a limit value relating to the setpoint value (setpoint value

 limit value). Each instance of limit

value monitoring issues an output signal.

Setup dialog

Parameters

Parameter

Selection/settings

Description

Alarm function

Inactive

Limit value monitoring is inactive.

AF1

Limit value above and below the set-
point value (monitoring band around the
setpoint value)

AF2

As for AF1, output signal inverted

AF3

Limit value below the setpoint value

AF4

As for AF3, output signal inverted

AF5

Limit value above the setpoint value

AF6

As for AF5, output signal inverted

AF7

Fixed limit value

AF8

As for AF7, output signal inverted

Signal suppres-
sion

Digital selector (Inactive)

Signal (high-active) for suppressing the
output signal

Actual value

Analog selector (Inactive)

Analog signal as actual value (signal to
be monitored)

Setpoint value

Analog selector (Inactive)

Analog signal as setpoint value (refer-
ence signal for AF1 to AF6)

?