11 Appendix

142

Pt1000

DIN EN 60751

-200 to +850 °C

50 ppm/K

2-wire circuit

 0.20 %

3-wire/4-wire circuit

 0.08 %

Ni100

DIN 43760

-60 to +250 °C

50 ppm/K

2-wire circuit

 0.36 %

3-wire/4-wire circuit

 0.24 %

Pt100

JIS 1604

-200 to +650 °C

50 ppm/K

2-wire circuit

 0.20 %

3-wire/4-wire circuit

 0.06 %

Pt50

GOST 6651-94

-200 to +1100 °C

50 ppm/K

2-wire circuit

 0.30 %

3-wire/4-wire circuit

 0.06 %

Pt100

GOST 6651-94

-200 to +850 °C

50 ppm/K

2-wire circuit

 0.15 %

3-wire/4-wire circuit

 0.05 %

Cu50

GOST 6651-94

-50 to +200 °C

200 ppm/K

2-wire circuit

 0.80 %

3-wire/4-wire circuit

 0.60 %

Cu100

GOST 6651-94

-50 to +200 °C

200 ppm/K

2-wire circuit

 0.80 %

3-wire/4-wire circuit

 0.50 %

KTY11-6

-50 to +150 °C

50 ppm/K

2-wire circuit

 1 %

3-wire/4-wire circuit

 0.24 %

Sensor lead resistance

Max. 30

 per lead for 3-wire and 4-wire circuit

Max. 10

 per lead for 2-wire circuit

Measuring current

Pt100 approx. 250

A, Pt500, and Pt1000 approx. 100 A; not con-

stant

Lead compensation

Not required for 3-wire and 4-wire circuit. For a 2-wire circuit, lead
compensation can be set in the software by correcting the actual
value.

1

The accuracy values refer to the maximum measuring range. Smaller measuring ranges lead to reduced lineariza-
tion accuracy.

Designation

Standard

Measuring range

Measuring accu-
racy

1

Ambient tempera-
ture influence