6 Configuration

70

6.9

Controller

Four controllers (controller channels) are available. The parameters listed here can be config-
ured independently of each other for controller 1 to controller 4.

6.9.1

Controller (features)

This screen is used to specify the name of the control loop, the controller type, the control di-
rection, and the output level for changeover to manual mode and for deviation above or below
the measuring range.

Setup dialog

Parameters

Parameter

Selection/settings

Description

Control loop
name

Use default text or select other text from
the list.

Designation of control loop

(The factory setting depends on the con-
troller channel.)

Controller type

Off

Controller channel is switched off

(factory setting for controller 2 to control-
ler 4)

Two-state controller

Controller with a switched output

(factory setting for controller 1)

Three-state controller

Controller with two continuous or
switched outputs (e.g. for heating/cool-
ing)

Modulating controller

Controller with two switched outputs (for
motor actuator)

?

?