5 controller, 6 electrical data, 5 controller 11.1.6 electrical data – JUMO 705010 mTRON T - Multichannel Controller Module Operating Manual User Manual
Page 145: 11 appendix
145
11 Appendix
Per optional board (option slot 1 to 3)
11.1.5
Controller
11.1.6
Electrical data
1 relay output (changeover contact)
Output 5, 7, and 9)
Switching capacity
3A at AC 230V resistive load
3A at DC 30V resistive load
Contact life
350,000 operations at rated load / 750,000 operations at 1 A
2 relay outputs (N/O contacts with common
pole)
(Output 5 to 10)
Switching capacity
3A at AC 230V resistive load
3A at DC 30V resistive load
Contact life
350,000 operations at rated load / 900,000 operations at 1 A
1 solid-state relay
(Output 5, 7, and 9)
Switching capacity
1 A at 230 V
Protection circuitry
Varistor
2 open-collector outputs
(Output 5 to 10)
Status logical "0” (transistor inhibited):
Allowable voltage via switching transistor
Min. 5 V, max. 30 V
Maximum reverse current
0.1 mA
Status logical "1” (transistor switched):
Maximum voltage via switching transistor
1.6 V
Maximum current
50 mA
Controller types
Two-state controller, three-state controller, modulating controller,
continuous controller, continuous controller with integrated actuator
controller
Controller structures
P, PD, PI, PID
Sampling rate
50 ms, 100 ms, 150 ms, 200 ms, or 250 ms
Voltage supply
Connection
Lateral (feed via base unit or router module)
Voltage input
DC 24 V +25/-20 %
Residual ripple
5 %
Current consumption
Max. 300 mA (at DC 19.2 V)
Power consumption
Max. 6 W
Inputs and outputs (terminals 1 to 28)
Connection
At the front (removable terminal strips with Push-In technology)
Conductor cross section on terminals 1 to 11
Wire or strand without ferrule
Min. 0.14 mm
2
, max. 1.5 mm
2
Strand with ferrule
Without plastic collar: Min. 0.25 mm
2
, max. 1.5 mm
2
With plastic collar: Min. 0.25 mm
2
, max. 0.5 mm
2