beautypg.com

5 controller, 6 electrical data, 5 controller 11.1.6 electrical data – JUMO 705010 mTRON T - Multichannel Controller Module Operating Manual User Manual

Page 145: 11 appendix

background image

145

11 Appendix

Per optional board (option slot 1 to 3)

11.1.5

Controller

11.1.6

Electrical data

1 relay output (changeover contact)

Output 5, 7, and 9)

Switching capacity

3A at AC 230V resistive load
3A at DC 30V resistive load

Contact life

350,000 operations at rated load / 750,000 operations at 1 A

2 relay outputs (N/O contacts with common
pole)

(Output 5 to 10)

Switching capacity

3A at AC 230V resistive load
3A at DC 30V resistive load

Contact life

350,000 operations at rated load / 900,000 operations at 1 A

1 solid-state relay

(Output 5, 7, and 9)

Switching capacity

1 A at 230 V

Protection circuitry

Varistor

2 open-collector outputs

(Output 5 to 10)

Status logical "0” (transistor inhibited):

Allowable voltage via switching transistor

Min. 5 V, max. 30 V

Maximum reverse current

0.1 mA

Status logical "1” (transistor switched):

Maximum voltage via switching transistor

 1.6 V

Maximum current

50 mA

Controller types

Two-state controller, three-state controller, modulating controller,
continuous controller, continuous controller with integrated actuator
controller

Controller structures

P, PD, PI, PID

Sampling rate

50 ms, 100 ms, 150 ms, 200 ms, or 250 ms

Voltage supply

Connection

Lateral (feed via base unit or router module)

Voltage input

DC 24 V +25/-20 %

Residual ripple

5 %

Current consumption

Max. 300 mA (at DC 19.2 V)

Power consumption

Max. 6 W

Inputs and outputs (terminals 1 to 28)

Connection

At the front (removable terminal strips with Push-In technology)

Conductor cross section on terminals 1 to 11

Wire or strand without ferrule

Min. 0.14 mm

2

, max. 1.5 mm

2

Strand with ferrule

Without plastic collar: Min. 0.25 mm

2

, max. 1.5 mm

2

With plastic collar: Min. 0.25 mm

2

, max. 0.5 mm

2