6 Configuration
Output value monitoring
Output level monitoring monitors the output level in the corrected state. The output level must
be within a definable range around a mean output level. If it is not, an alarm is issued.
The alarm signal is only available within the multichannel controller module in the digital selec-
tor (no transfer via system bus). It can, however, be selected as an input signal for the collective
alarm of the controller channel.
Setup dialog
Parameters
Parameter
Selection/settings
Description
Monitoring
Permitted
Output level monitoring depends on the
"Activation" parameter.
Not permitted
Output level monitoring is blocked.
Determination
time
0 s to 350 s to 9999 s
Calculation time for the mean output
level
Output level band 0 % to 10 % to 100 %
Monitored output level band (admissible
range around the mean output level)
Alarm delay
0 s to 9999 s
Delay time for alarm triggering
Control diff. band 0 to 1 to 1999
Control differential band (admissible
range around the actual value in cor-
rected state)
Activation
Digital selector (Inactive)
Signal (high-active) to activate the out-
put level monitoring
Inactive = Output level monitoring is only
dependent on the "Monitoring" parame-
ter (it is active if Monitoring = Permitted).