6 Configuration

Output value monitoring

Output level monitoring monitors the output level in the corrected state. The output level must
be within a definable range around a mean output level. If it is not, an alarm is issued.
The alarm signal is only available within the multichannel controller module in the digital selec-
tor (no transfer via system bus). It can, however, be selected as an input signal for the collective
alarm of the controller channel.

Setup dialog

Parameters

Parameter

Selection/settings

Description

Monitoring

Permitted

Output level monitoring depends on the
"Activation" parameter.

Not permitted

Output level monitoring is blocked.

Determination
time

0 s to 350 s to 9999 s

Calculation time for the mean output
level

Output level band 0 % to 10 % to 100 %

Monitored output level band (admissible
range around the mean output level)

Alarm delay

0 s to 9999 s

Delay time for alarm triggering

Control diff. band 0 to 1 to 1999

Control differential band (admissible
range around the actual value in cor-
rected state)

Activation

Digital selector (Inactive)

Signal (high-active) to activate the out-
put level monitoring

Inactive = Output level monitoring is only
dependent on the "Monitoring" parame-
ter (it is active if Monitoring = Permitted).