6 Configuration
Control loop name
Setup program: Selection of text from a list
Click the "..." button to open a list with the text numbers and the associated texts. The texts can
be edited.
Multifunction panel: selection of text using the text number
The setup program is required to view and edit the texts.
Controller type
Description of controller types:
Chapter 7.2 "Controller types", page 119
Controller type
(continued)
Continuous controller
Controller with a continuous output
(analog signal)
Position controller
Continuous controller with integrated
position controller (for motor actuator)
Control direction
Direct
The controller output level is positive if
the actual value is greater than the set-
point value (cooling).
Inverse
The controller output level is positive if
the actual value is smaller than the set-
point value (heating).
Last y at man.
mode
Transfer of the last output level at changeover to manual mode
Not selected (empty)
Output level is not transferred ("Manual
output level" parameter is active).
Selected (checkmark)
Output level is transferred ("Manual out-
put level" parameter is not active).
Manual output
level
0 to 100
(-100 to +100 for three-state controller)
Output level (%) after changeover to
manual mode
Last y at
O-o-R
Transfer of the last output level in the event of deviation above or below the mea-
suring range (out of range = O-o-R)
Not selected (empty)
Output level is not transferred ("y (outp.
level) at O-o-R" parameter is active).
Selected (checkmark)
Output level is transferred ("y (outp.
level) at O-o-R" parameter is not active).
y (outp. level) at
O-o-R
0 to 100
(-100 to +100 at three-state controller)
Output level (%) in the event of deviation
above or below the measuring range
Unit
5 characters (%)
Unit for numerical representation of the
actual value and setpoint value on con-
troller screen
Last w at inde-
pendent mode
The last valid setpoint value is retained at changeover to independent mode.
Not selected (empty)
Setpoint value can change (depending
on configuration).
Selected (checkmark)
Setpoint value is retained.
Parameter
Selection/settings
Description