6 Configuration

Control loop name

Setup program: Selection of text from a list
Click the "..." button to open a list with the text numbers and the associated texts. The texts can
be edited.
Multifunction panel: selection of text using the text number
The setup program is required to view and edit the texts.

Controller type

Description of controller types:
Chapter 7.2 "Controller types", page 119

Controller type

(continued)

Continuous controller

Controller with a continuous output
(analog signal)

Position controller

Continuous controller with integrated
position controller (for motor actuator)

Control direction

Direct

The controller output level is positive if
the actual value is greater than the set-
point value (cooling).

Inverse

The controller output level is positive if
the actual value is smaller than the set-
point value (heating).

Last y at man.
mode

Transfer of the last output level at changeover to manual mode

Not selected (empty)

Output level is not transferred ("Manual
output level" parameter is active).

Selected (checkmark)

Output level is transferred ("Manual out-
put level" parameter is not active).

Manual output
level

0 to 100

(-100 to +100 for three-state controller)

Output level (%) after changeover to
manual mode

Last y at
O-o-R

Transfer of the last output level in the event of deviation above or below the mea-
suring range (out of range = O-o-R)

Not selected (empty)

Output level is not transferred ("y (outp.
level) at O-o-R" parameter is active).

Selected (checkmark)

Output level is transferred ("y (outp.
level) at O-o-R" parameter is not active).

y (outp. level) at
O-o-R

0 to 100

(-100 to +100 at three-state controller)

Output level (%) in the event of deviation
above or below the measuring range

Unit

5 characters (%)

Unit for numerical representation of the
actual value and setpoint value on con-
troller screen

Last w at inde-
pendent mode

The last valid setpoint value is retained at changeover to independent mode.

Not selected (empty)

Setpoint value can change (depending
on configuration).

Selected (checkmark)

Setpoint value is retained.

Parameter

Selection/settings

Description