Gen Alert
can be used as a limited-functionality controller for an AC generator with a remote-start feature. It
can start and stop the generator based on DC (battery) voltage levels.
This function has settable DC voltage and time parameters.
NOTE: This option does not have the same advantages as the Advanced Generator Start (AGS) function
which is controlled directly by the MATE3. (See page 115.)
Figure 108 Gen Alert
Fault
activates the AUX output when the inverter shuts down due to an error condition (see page 43). It can
operate a light or alarm to show that the inverter has failed. This function has no settable parameters. The
screen is shown on page 93.
Vent Fan
activates the AUX output in response to high DC (battery) voltage. It can operate a small fan to
ventilate the battery compartment to eliminate gases that result from battery charging.
This function has settable DC voltage and time parameters.
Figure 109 Vent Fan
Cool Fan
activates the AUX output when the inverter reaches a high internal temperature. It is intended to
operate a small external fan for additional cooling. This includes sealed inverter models which come with a
Turbo fan.
This function has no settable parameters. The AUX output deactivates after reaching a
cooler temperature.
DC Divert
activates the AUX output to divert excess energy to a DC load, in response to high DC (battery)
voltage. The AUX output operates a larger relay, which allows current to flow to a dedicated DC load when
energized. The output deactivates following a delay when a low DC voltage setting is reached.
This option has settable DC voltage and time parameters.
Figure 110 Divert DC
Set Points:
ON: Batt – Sets the high-voltage level at which the
DC Divert function activates the AUX output.
Delay – Sets the delay time after the ON: Batt setting is
reached before the AUX output is activated.
OFF: Batt – Sets the low-voltage level at which the
DC Divert function deactivates the AUX output.
Delay – Sets the delay time after the OFF: Batt setting is
reached before the AUX output is deactivated.
Set Points
:
ON: Batt – Sets the high-voltage level at which the function
activates the AUX output. It remains active for one minute.
OFF: Delay – Sets the delay time before the function
activates the AUX output again.
Set Points
:
ON: Voltage – Sets the low-voltage level at which the
Gen Alert function activates the AUX output.
Delay – Sets the delay time after the ON: Voltage setting is
reached before the AUX output is activated.
OFF: Voltage – Sets the high-voltage level at which the
Gen Alert function deactivates the AUX output.
Delay – Sets the delay time after the OFF: Voltage setting is
reached before the AUX output is deactivated.