beautypg.com

High battery transfer (hbx), Programming – Outback Power Systems MATE3 Owners Manual User Manual

Page 126

background image

Programming

124

900-0117-01-00 Rev C

High Battery Transfer (HBX)

In High Battery Transfer (HBX) mode, the system is connected to an AC source such as the utility grid;
however, it will use battery power as the first priority. The AC source is locked out until needed.

In this mode, the system runs on battery-supplied power for as long as the batteries can be sustained. It is
expected that the batteries will also be charged from renewable sources such as PV power. When the
batteries become depleted, the system reconnects to the AC source to operate the loads.

The batteries may be recharged during this time using the renewable source. When the batteries are
recharged to a high enough voltage, the system transfers back to the batteries as the primary source
(hence the name High Battery Transfer).

NOTE: In Radian-class inverters, the

Mini Grid

input mode can also accomplish this operation; however,

it is not identical to HBX and is not compatible with it. Both functions should not be used at the same
time. HBX is a function of the MATE3 while

Mini Grid

is a function of the inverter, which is programmed

using the MATE3. Information on selecting

Mini Grid

can be found on page 86. Information on

Mini Grid

and other input modes can be found in the Radian Series Inverter/Charger Operator’s Manual.

NOTE: For best operation, the inverter’s charger should be turned off when HBX mode is in use. HBX
mode is intended for systems that rely primarily on the renewable energy source for charging. The
settings of HBX mode allow it to disconnect from the utility grid whenever it can charge effectively using
the renewable source. Use of the inverter's charger may interfere with these priorities. This may keep
both HBX mode and the inverter's charger from working effectively.

 See page 56 (the

CHARGER hot key) for instructions on shutting off the charger function.

HBX Mode commands the inverter to:

 connect to an AC source if the battery voltage has fallen below the

Grid Connect

voltage for the amount of time

set in the (connect)

Delay

set point,

 connect to an AC source if the battery state of charge (SOC) has fallen below the

Grid Connect SOC

for any

amount of time,

 disconnect the AC source and switch to powering the loads from the battery bank if the battery voltage has risen

above the

Grid Disconnect

voltage for the amount of time set in the (disconnect)

Delay

set point, and

 disconnect the AC source and switch to powering loads from the battery bank if the battery state of charge

(SOC) has risen above the

Grid Disconnect SOC

for any amount of time.

The

Delay

set points are used to prevent the inverter from switching to grid power in the event

of a sudden, sizable demand for power that may momentarily drop the voltage below the

Grid Connect

value.

The

SOC

set points are only usable by a system equipped with a battery monitor.

Table 3

HBX Mode Default Set Points

System Voltage

12 V

24 V

36 V

48 V

High

Voltage 13 26 38 52

Low

Voltage

12 24 36 48

Time

1 hour

1 hour

1 hour

1 hour

NOTE: The system must be in the

Grid Disconnect

state to allow HBX default settings to be changed.