beautypg.com

Ags state-of-charge (soc) start, Ags must run schedule, Ags quiet time schedule – Outback Power Systems MATE3 Owners Manual User Manual

Page 121: Mate3 settings

background image

MATE3 Settings

900-0117-01-00 Rev C

119

AGS State-of-Charge (SOC) Start

With a FLEXnet DC, a generator can be started or stopped based on the battery state of charge (SOC)
rather than voltage. However, this feature may become less accurate if the system routinely cycles
without obtaining a full charge for long periods of time.

The

Enable Full Charge

set point overrides the

Stop SOC

function by establishing a time period from 1

to 30 days. At the end of this time, the batteries will be charged to 100% regardless of the SOC value.

When

Enable Full Charge

is set to

Y

, the MATE3 will compare the

Days Since Parms Met

display

(

415H422H

Figure 35) against the

Interval days

shown in

416H423H

Figure 127. If

Days Since Parms Met

is equal or higher,

then the generator will run until the FLEXnet DC's charge parameters are met. More information on this
function is available on page 152.

Setting

Enable Full Charge

to

N

or setting the

Interval days

to zero (0) days will disable the function.

Figure 147 MATE3/AGS/State-of-Charge Start Screen

AGS Must Run Schedule

Must Run Schedule

time is a daily time period when the MATE3 commands the generator to run. This is

usually set because large loads are expected to be present.

Must Run Schedule

times can be set

individually for weekdays and weekends.

Setting start and stop times to the same time disables the

Must Run Schedule

function.

Figure 148 MATE3/AGS/Must Run Schedule Screen

AGS Quiet Time Schedule

Quiet time is a period of time when the generator should not run, due to the risk of inappropriate noise or
other reasons.

Setting start and stop times to the same time disables the Quiet Time function.

Set Points:

EnableN = No, Y = Yes
Start SOC 0 to 99%
Stop SOC 0 to 100%
Enable Full Charge N = No, Y = Yes
Interval Days 1 to 30 days; this is the time in days used by

the

Enable Full Charge (100% SOC) function and the FNDC’s

charging parameters.

Set points:

EnableN = No, Y = Yes
Weekday Start 00:00 to 23:59
 Weekday Stop00:00 to 23:59
Weekend Start 00:00 to 23:59
 Weekend Stop 00:00 to 23:59