beautypg.com

Start and stop reasons for the ags function, Troubleshooting, Load kw – Outback Power Systems MATE3 Owners Manual User Manual

Page 154: Table 5 ags start and stop reasons, Stop reasons, Start reasons

background image

Troubleshooting

152

900-0117-01-00 Rev C

Start and Stop Reasons for the AGS Function

The first two columns in this table is the list of Automatic Generator Start reasons which may be displayed
in the

Gen hot key screen as shown in Figure 54. The remaining columns display all possible reasons for

the generator to automatically stop. The possible stop reasons are related to the start reason.
For example, a generator which started due to

Load kW

can stop due to reduction of load kilowatts, due

to Quiet Time, or manually, but it will not stop due to SOC or for any of the other reasons.

Table 5

AGS Start and Stop Reasons

STOP REASONS

Inverter

in Float

or Silent

Stop SOC

%

Stop at

100%

SOC

FNDC

Charge

Parms

Met

(CPM)

Below

Load kW

Quiet

Time

Exercise

Time

Expires

Manual

Stop

High

Bat

Voltage

Must

Run

Stop

START

REASONS

Global

Rebulk

2 Min Batt V

yes

stop

Stop

stop

stop

2 Hour Batt V

yes

stop

Stop if

days since

CPM

< setting

Stop if

days since

100% SOC

> setting

Stop if days

since CPM

> setting

stop stop

stop

24 Hour Batt V

yes

stop

Stop if

days since

CPM

< setting

Stop if

days since

100% SOC

> setting

Stop if days

since CPM

> setting

stop stop

stop

Start Soc%

yes

stop

Stop if

days since

CPM

< setting

Stop if

days since

100% SOC

> setting

Stop if days

since CPM

> setting

stop stop

stop

Load kW

stop

stop

stop

Exercise

stop

stop

stop

Must Run Start

yes

stop

stop

stop

Manual Start

yes

if auto

selected

if auto

selected

stop

NOTES:

 "Setting" refers to the "Interval Days" setting in the State of Charge Start screen as depicted in Figure 127.
 CPM, or Charged Parameters Met, refers to the FNDC's full-charge parameters as defined on page 48.
 The conditions of the "Inverter In Float or Silent" column will stop the generator if the inverter reaches these stages before the conditions of the

other columns take effect.

 The conditions of the Stop SOC% column apply as long as "Days Since Parms Met" does not exceed "Interval Days". The generator will be shut off

upon reaching the "Stop SOC%" setting as shown in Figure 127.

 The conditions of the Stop at 100% SOC column apply if "Days Since Parms Met" equals or exceeds "Interval Days." The generator will ignore the

Stop SOC% setting and continue running until the battery SOC is at 100%. (This function does not operate if Enable Full Charge is set at N, or if the
Interval is set at 0.)

The conditions of the FNDC Charge Parms Met (CPM) column apply when "Days Since Parms Met" equals or exceeds "Interval Days" and Enable Full
Charge (100% SOC) is disabled as noted above. These conditions also apply if for any reason the charge parameters are not met when the batteries
reach 100% SOC as noted above. The generator will continue to run until the FNDC's charge parameters have been met.