Operation

62

900-0117-01-00 Rev C

AC INPUT Hot Key

The

AC INPUT hot key displays the

AC Input Status

screen. The

AC Input Status

screen displays the

AC input mode, the AC input status, and the current AC frequency and voltage. Soft key options include
manually using or dropping the AC input source or viewing the

Last AC Disconnect

screen. The

Last AC Disconnect

screen indicates the reason the AC source may have been disconnected. These

reasons will vary between inverter models. See the inverter Operator’s Manual for more information on
troubleshooting a specific message.

Figure 62

Using the AC INPUT Hot Key

Figure 63

AC Disconnect Reasons

AC INPUT Hot Key

Soft Key Options:

returns to the Home screen.

manually disconnects the system
from the AC source.

instructs the inverter to use
the AC source if the AC source meets
qualification parameters.

displays a screen that shows the
reason for the last AC disconnect.

Screen Items:

AC Input Select (Radian-class only) displays which of two
inputs was set as first priority for the inverter. See page 83.
This item is not present in FX-class inverters.

AC Input Mode allows soft key options to be selected to
change the mode. This item may be overridden by other
commands. For example, a system that is set to

DROP will

automatically switch to

USE if AGS starts the generator.

Next to the current

AC Input Mode is the last reason the

status was changed. In this illustration, the status changed
due to an

HBX-SOC event. Other possible reason for a status

change are

Manual, AGS, Grid-Time, or HBX-Voltage.

AC Input Status displays the current interaction with the AC
input. This screen will usually change to match

AC Input

Mode once a soft key command is given.

NOTE: In Radian-class inverters, the displayed AC voltage is

the sum of the L1 and L2 phases.

Soft Key Options:

returns to the

AC Input Status screen.

cycles through all the devices connected to the HUB.

Screen Items (all inverters):

Input Frequency Too High, N = No, Y = Yes

Input Frequency Too Low, N = No, Y = Yes

Input Voltage > Maximum, N = No, Y = Yes

Input Voltage < Minimum, N = No, Y = Yes

Additional Screen Items (Radian-class only)

Backfeed, N = No, Y = Yes

Phase Lock, N = No, Y = Yes

Island Detect, N = No, Y = Yes