Programming – Outback Power Systems MATE3 Owners Manual User Manual

Page 86

background image

Programming

84

900-0117-01-00 Rev C

NOTE:

In FX-class grid-interactive inverters,

Input Type

also controls the cycle used by the inverter’s battery

charger. This overrides the selections offered in the

Charger Status

screen. (See page 56.)

Grid

selects a charge cycle consisting of bulk, absorption, and float stages. Upon completion, the charger goes

into Silent mode until it reaches the “re-float” voltage, when it will re-enter the float stage.

Gen

selects a charge cycle consisting of bulk, absorption and float stages. Upon completion, the charger

remains in the float stage to maintain the batteries until the AC input is disconnected.

IMPORTANT:

The

Input Type

selection also controls other AC source parameters, as

described in the inverter Operator’s Manual. If

Gen

is selected, a

grid-interactive inverter will not sell power. However, the AGS function
(see page 116) will function even if

Grid

is selected.

The above material does not apply to Radian-class inverters, or to FX-class inverters without
grid-interactive functions.

IMPORTANT:

Selecting the charge cycle does not automatically activate the charger. If the
charger is deactivated, it must still be activated using the

Charger Status

screen. (See page 56.)