beautypg.com

Ags setup, Programming – Outback Power Systems MATE3 Owners Manual User Manual

Page 118

background image

Programming

116

900-0117-01-00 Rev C

Figure 142 Advanced Generator Start (AGS) Menu

AGS Setup

Figure 143 AGS Setup Screen

Set Points:

AGS Enabled either enables (Y) or disables (N) the AGS mode.
Port identifies the HUB port (1 – 10) for the device that is

going to control the generator.

Fault Time is the period the generator is given to connect to

the inverter system after the AUX output has been activated.
If the generator fails to connect and provide AC current during
this time, the MATE3 displays an

AGS Fault message on the

Gen screen.

A fault is added to the event log and the Event

LED will illuminate. This set point can be anywhere from

5 to

30 minutes.

Control (Radian-class only) selects which terminals will be

used for AGS: AUX Output or AUX Relay.

Warmup Time for the generator (in minutes). Before

charging begins, the

Warmup Time allows the user to adjust

the time the generator will be allowed to run with no load.
This time can be from

0 to 30 minutes, but should follow the

generator manufacturer’s recommendations.

Cool Down Time for the generator (in minutes). After

charging has stopped, the

Cool Down Time

set point

allows

the user to adjust the time the generator will run with no load
before being shut off. This time can be from

0 to 30 minutes,

but should follow the generator manufacturer’s
recommendations.

DC Generator identifies if a DC generator is used, instead of

an AC generator.

~

DC Absorb Time is the amount of time that the batteries
must remain at the

DC Absorb Voltage. Once this time

expires, the MATE3 can shut the generator off.

~

DC Absorb Voltage is the voltage the batteries must
reach while being charged by a DC generator before the
DC absorb timer starts counting.

~

The

Stop SOC %

setting (see page 119) can also be used

to stop a DC generator.

~

These settings only become effective when
DC Generator is set to Y.

NOTE:

 If there is only one inverter in the system and

no OutBack HUB is used, it is necessary to set
the AGS Port to zero (0).

 If a HUB is used, adjust the port number to the

port that is assigned to the device that is
going to control the generator.

 In an example of a common configuration:

~

Ports 1-4 are for the inverters.

~

Ports 5-7 are for the charge controllers.

 It will be necessary to choose which device is

going to control the generator (1, 2, 3, or 4)
and set that number as the AGS port in that
menu.

IMPORTANT:

 Cool Down and Warmup times are

disabled when a DC generator is used.

 If an AC generator is being used, the

DC Generator menu item must be set
to

N.