Set generator total run time, Ags timers, Mate3 settings – Outback Power Systems MATE3 Owners Manual User Manual
Page 123
MATE3 Settings
900-0117-01-00 Rev C
121
Set Generator Total Run Time
The total running time for an automatic generator is displayed on the
Generator Status
screen, which is
accessed with the
Gen hot key. (See page 59.) This menu allows the timer to be set to a different figure,
or to be reset to zero.
Figure 151 MATE3/AGS/Set Generator Total Run Time
AGS Timers
The
AGS Timers
screen is a read-only screen that provides the following information. Programming of
these values is done in the
Quiet Time Schedule, Voltage Start, Load Start, Must Run Schedule,
or
State of Charge Start
menus described on pages 116
through 119.
Figure 152 MATE/AGS/ AGS Timers Screen
Set points:
Generator Total Run Time – 0.0 to 999.9 hours
Fault begins counting from zero
when no voltage is detected after a
generator start. When the
Fault Time setting is reached
according to the
AGS Setup screen
on page 116, an AGS fault will be
generated and an event will be
recorded (see page 61).
Warmup, Cool down, and
Exercise begin counting from zero
when each stage begins. The
generator will react accordingly
when their respective times are
reached according to the
AGS Setup screen on page 116.
2 Min, 2 Hour, and 24 Hour
begin counting down from
the maximum time when
the respective conditions
are reached for each setting.
If any of these timers reach
zero, the generator will
be started.
Load Start and Load Stop begin
counting from zero when the
respective conditions are reached
for each setting. If either of these
timers reach the delay time as set
in the
Load Start screen on
page 118, the generator will be
started or stopped as appropriate.
DC Absorb is used with the DC
generator settings shown in
423H430H
Figure 123 on page 116. It begins
counting from zero when the
DC Absorb Voltage is reached.
The generator will be stopped
when the
DC Absorb Time
setting is reached.
Screen Items: