Auxiliary output (aux modes, radian-class only), Inverter settings – Outback Power Systems MATE3 Owners Manual User Manual
Page 95
Inverter Settings
900-0117-01-00 Rev C
93
Auxiliary Output (AUX Modes, Radian-class only)
The
Auxiliary Output
controls the functionality of a Radian-class inverter’s Auxiliary (AUX) output. The
inverter’s AUX terminals provide a 12 Vdc output that can deliver up to 0.7 Adc to control external loads.
Typical loads include signaling a generator to start, sending a fault alarm signal, or running a small fan to
cool the inverter. See the inverter Installation Manual for more information on hooking up the AUX
terminals.
NOTE: The Radian inverter is equipped with two sets of AUX terminals: Auxiliary Output and Auxiliary
Relay, each with its own menu. These menus control the output and functionality of the AUX output.
Figure 106 Auxiliary Output
Auxiliary modes include the following:
Load Shed
can perform load management. When battery voltage rises above a settable high voltage level, the
AUX output is activated after a settable delay. The AUX output is used to operate a relay, which is connected to
non-vital loads. The AUX output will be deactivated once the battery voltage falls below a low voltage setting for
a settable delay period. See the Operator’s Manual for other conditions when this function may bedeactivated.
This function has settable DC voltage and time parameters.
Figure 107 Load Shed
Set Point:
ON: Batt – Sets the high-voltage level at which the
Load Shed function activates the AUX output.
Delay – Sets the delay time after the ON: Batt setting is
reached before the AUX output is activated.
OFF: Batt – Sets the low-voltage level at which the
Load Shed function deactivates the AUX output.
Delay – Sets the delay time after the OFF: Batt setting is
reached before the AUX output is deactivated.
Set Points:
Status – The AUX output status is controlled by the
~
Auxiliary Output immediately. It will
display the message
Manual On and remain continuously
active until
~
Auxiliary Output by automatic criteria,
according to the option selected in Aux Mode. When
activated, it displays the message
Auto On; otherwise it
displays
Auto Off.
~
Auxiliary Output and prevents any of
the inverter’s automatic AUX options from working. When
Manual Off. Note that even if
the AUX output is set to
Off, it may still be activated by an
external option not based in the inverter, such as AGS.
(See page 115.) If this soft key is pressed, the screen will
display
Manual Off.
Aux Mode – Selects one of nine functions with automatic criteria.
(These functions are described briefly in the next section and in
greater detail in the inverter Operator’s Manual.)
Aux Modes:
Load Shed
Gen Alert
Fault
Vent Fan
Cool Fan
DC Divert
IEEE
Source Status
AC Divert
Auxiliary Output Screen (Radian-class)