Figure 160 FLEXnet DC Advanced Control

Set Points:

Enable Charge Termination Control - allows the battery charging to be stopped for all

inverters on the system, once the charging parameters of the FLEXnet DC have been met.
(See page 112 for these parameters.) Options are

N (no) or Y (yes).

Enable Auto Grid-Tie Control - If grid-interactive inverters are present on the system, this

control allows their grid-interactive function to be turned off at midnight each night. If
grid-interactive inverters are not present, this item is inoperative. Options are

N (no) or

Y (yes). When Y is selected, "grid-tie" mode will be enabled on grid-interactive inverters
anytime the battery monitor signals that charge parameters have been met.

NOTE: When grid-tie mode is enabled with this function, the

Grid-Tie Enable menu item

(see page 101) will change to

Y (yes). The inverter will become capable of selling even if

the function had been previously turned off.

The next two items are both related to the system indicators on the Home screen (see pages 33
and 151) and are titled

Battery Status on the screen.

Low SOC Warning Level If the batteries decrease to this state of charge (SOC), an event

will be registered in the event log, and the Home screen will display !

, a battery

warning. Settable range is

20% to 99%.

Critical SOC Warning Level If the batteries decrease to this state of charge (SOC), an

event will be registered in the event log, and the Home screen will display X

, a warning

that the batteries have been critically discharged. Settable range is

10% to 98%.