Port card menu – HP StorageWorks 2.64 Director Switch User Manual
Page 68
Monitoring and managing the director
68
•
10 Port binding violation - Unauthorized WWN
—The WWN that was entered
to configure Port Binding for this port is not valid, or a nickname was used that was not
configured for the attached device in the Element Manager.
•
11 Unresponsive node connected to port
—Possible causes are: (1) a hardware
problem on a switch or connected node where ELP frames are not delivered; the response is
not received, or a fabric login (FLOGI) cannot be received (there may be problem in the
switch SBAR); (2) a faulty or dirty cable connection; (3) faulty host bus adapters that do not
send out a FLOGI within a reasonable timeframe.
Reason messages for an inactive state include:
•
1 Switch speed conflict
(Director 2/64 model only)—The director data speed was
set to 2 Gb/s), but the port only supports 1 Gb/s operation because it is on an FPM port
card. (All ports on all installed FPM cards will go inactive if the director data speed is set to
2 Gb/s.) To activate the port, either set the director data speed to 1 Gb/s (1 Gig) through
the Configure Switch Parameters dialog box, or replace the FPM card with a UPM card.
•
2 Optics speed conflict
(Director 2/64 model only)—The port data speed was set
to 2 Gb/s, but the director data speed was set to 1 Gb/s. To activate the port, set the
director data speed to 2 Gb/s (2 Gig) through the Configure Switch Parameters dialog box.
Note that a port could also be inactive if the card is an FPM card and the port data speed
was set to 2 Gb/s. To activate the port in this case, set director data speed to 1 Gb/s, or
replace the FPM card with a UPM card.
NOTE:
Note that your director model and firmware may not allow variable data speed settings.
•
Threshold Alert—If a threshold alert exists for the port, an alert indicator (yellow triangle)
displays by the Threshold Alert field, and the configured name for the last alert received
displays in the field.
•
Zoning Enforcement—For directors, this field displays Soft zoning for ports using soft zoning
and Hard zoning for ports using hard zoning.
Port Card menu
While in the Port Card view, right-click the card away from a port connector to display a pop-up
menu of port card functions.
•
Block All Ports—Click this option to display the Block All Ports dialog box. Click Yes to block all
ports on the selected card or click No to cancel.
•
Unblock All Ports—Click this option to display the Unblock All Ports dialog box. Click Yes to
unblock all ports on the selected card or No to cancel.
•
Diagnostics—Click this option to display the Port Diagnostics dialog box. Use this dialog box to
run internal loopback and external loopback tests on any port or all ports on the port card. For
instructions on using these diagnostics, refer to the HP StorageWorks Director 2/64 service
guide for the Director 2/64 and the HP StorageWorks Director 2/140 service guide for the
Director 2/140.