NORD Drivesystems BU0180 User Manual

Page 96

background image

SK 180E Manual for frequency inverters

96

Pre-series version

BU 0180 GB-0914

Parameter

{Factory setting}

Setting value / Description / Note

Device

Supervisor

Parameter
set

P402

[-01]

...

[-06]

Adjustment: 0%

(Analog input adjustment: 0%)

S

-50.00 ... 50.00 V

{ all 0.00 }

[-01] = Analog input 1, Function of analog input 1 integrated into the FI

[-02] = Analog input 2, Function of analog input 2 integrated into the FI

[-03] = Ext. Analog input 1,

AIN1 of the first I/O extension (SK xU4-IOE)

[-04] = Ext. Analog input 2,

AIN2 of the first I/O extension (SK xU4-IOE)

[-05] = Ext.

A.in

1 2nd IOE,

AIN1 of the second I/O extension (SK xU4-IOE)

[-06] = Ext.

A.in

2 2nd IOE,

AIN2 of the second I/O extension (SK xU4-IOE)

This parameter sets the voltage which should correspond with the minimum value of the selected
function for the analog input 1 or 2. In the factory setting (setpoint) this value is equivalent to the
setpoint set via P104 >Minimum frequency<.

Note
SK 1x0E
For the adjustment of the integrated analog inputs of the SK1x0E to the type of analog signals, the
following values must be set:

0

– 10 V

→ 0.00 V

2

– 10 V

→ 2.00 V

0

– 20 mA → 0.00 V (switch in internal resistance via DIP switch S1 (Section.: 5.2.2.2)

4

– 20 mA → 1.00 V (switch in internal resistance via DIP switch S1 (Section.: 5.2.2.2)

SK xU4-IOE
Standardisation to typical signals, such as 0(2)-10V or 0(4)-20mA is carried out via the DIP switch
on the I/O-extension module. In this case, additional adjustment of parameters (P402) and (P403)
must not be carried out.

P403

[- 01]

...

[- 06]

Adjustment: 100%

(Analog input adjustment: 100%)

S

-50.00 ... 50.00 V

{ all 0.00 }

[-01] = Analog input 1, Function of analog input 1 integrated into the FI

[-02] = Analog input 2, Function of analog input 2 integrated into the FI

[-03] = Ext. Analog input 1,

AIN1 of the first I/O extension (SK xU4-IOE)

[-04] = Ext. Analog input 2,

AIN2 of the first I/O extension (SK xU4-IOE)

[-05] = Ext.

A.in

1 2nd IOE,

AIN1 of the second I/O extension (SK xU4-IOE)

[-06] = Ext.

A.in

2 2nd IOE,

AIN2 of the second I/O extension (SK xU4-IOE)

This parameter sets the voltage which should correspond with the maximum value of the selected
function for the analog input 1 or 2. In the factory setting (setpoint) this value is corresponds with
the setpoint set via P105 >Maximum frequency<.

Note
SK 1x0E
For the adjustment of the integrated analog inputs of the SK1x0E to the type of analog signals, the
following values must be set:

0

– 10 V

→ 10.00 V

2

– 10 V

→ 10.00 V

0

– 20 mA → 5.00 V (switch in internal resistance via DIP switch S1 (Section.: 5.2.2.2)

4

– 20 mA → 5.00 V (switch in internal resistance via DIP switch S1 (Section.: 5.2.2.2)

SK xU4-IOE
Standardisation to typical signals, such as 0(2)-10V or 0(4)-20mA is carried out via the DIP switch
on the I/O-extension module. In this case, additional adjustment of parameters (P402) and (P403)
must not be carried out.