SK 180E Manual for frequency inverters
160
Pre-series version
BU 0180 GB-0914
9.2.2
Process controller parameter settings
(Example: Setpoint frequency: 50 Hz, control limits: +/- 25%)
P105 (maximum frequency) [Hz]
:
%
100
%
415
.
q
Setpointfr
.
q
Setpointfr
P
Hz
Hz
Example:
%
100
%
25
50
50
Hz
Hz
62.5 Hz
P400 [-01] (Funct. Analog input1)
:
“2” (frequency addition)
P411 (setpoint frequency) [Hz]
: Set frequency with 10 V at analog input 1
Example: 50 Hz
P412 (Process controller setpoint) : CR middle position / Default setting 5V (adjust if necessary)
P413 (P controller) [%]
: Factory setting 10% (adjust if necessary)
P414 (I-controller) [% / ms]
: recommended 100%/s
P415 (limitation +/-) [%]
: Controller limitation (see above)
Note:
Parameter P415 is used as a control limit after the PI controller.
Example: 25% of setpoint
P416 (Ramp time PI setpoint) [s]
: Factory setting 2s (if necessary, adjust to match controller behaviour)
P420 [-01] (Funct. digital input 1)
: "1" Enable right
P400 [-02] (Funct. Analog input 2) : "6" PI process controller actual value