9.2.2

Process controller parameter settings

(Example: Setpoint frequency: 50 Hz, control limits: +/- 25%)

P105 (maximum frequency) [Hz]

:

 

 

 

%

100

%

415

.

q

Setpointfr

.

q

Setpointfr

P

Hz

Hz

Example:

%

100

%

25

50

50

Hz

Hz

62.5 Hz

P400 [-01] (Funct. Analog input1)

:

“2” (frequency addition)

P411 (setpoint frequency) [Hz]

: Set frequency with 10 V at analog input 1


Example: 50 Hz

P412 (Process controller setpoint) : CR middle position / Default setting 5V (adjust if necessary)

P413 (P controller) [%]

: Factory setting 10% (adjust if necessary)

P414 (I-controller) [% / ms]

: recommended 100%/s

P415 (limitation +/-) [%]

: Controller limitation (see above)

Note:

Parameter P415 is used as a control limit after the PI controller.

Example: 25% of setpoint

P416 (Ramp time PI setpoint) [s]

: Factory setting 2s (if necessary, adjust to match controller behaviour)

P420 [-01] (Funct. digital input 1)

: "1" Enable right

P400 [-02] (Funct. Analog input 2) : "6" PI process controller actual value