NORD Drivesystems BU0180 User Manual
Page 103
6 Parameterisation
BU 0180 GB-0914
Pre-series version
103
Value Function
Description
Signal
74 ²
Left block+ Fast
"Block left rotation + emergency
stop"
As for setting 32, however coupled to the function "Fast Stop".
Low
75
Dig.out. 2 man/auto set
"Set digital output 2 manually /
automatically"
As for function 67, however for digital output 2
High
76
Dig.out. 2 man. set
"Set digital output 2 manually"
As for function 68, however for digital output 2
High
77
Reserved
1
If neither of the digital inputs is programmed for left or right enable, then the actuation of a fixed frequency or jog frequency will
enable the frequency inverter. The rotation field direction depends on the sign of the setpoint.
2
Also effective for bus control (RS232, RS485, CANbus, CANopen, DeviceNet, Profibus, InterBus, AS-Interface)
3
Function cannot be selected via BUS IO In Bits
Parameter
{Factory setting}
Setting value / Description / Note
Device
Supervisor
Parameter
set
P426
Quick stop time
(Quick stop time)
S
P
0 ... 320.00 sec
{ 0.10 }
Setting of the stop time for the fast stop function which can be triggered either via a digital input,
the bus control, the keyboard or automatically in case of a fault.
Emergency stop time is the time for the linear frequency decrease from the set maximum
frequency (P105) to 0Hz. If an actual setpoint <100% is being used, the emergency stop time is
reduced correspondingly.
P427
Emerg. stop on error
(Emergency stop on fault)
S
0 ... 3
{ 0 }
Activation of automatic emergency stop following error
0 = Disabled: Automatic emergency stop following fault is deactivated
1 = Mains supply failure: Automatic emergency stop following mains supply failure
2 = In case of faults: Automatic emergency stop following error
3 = Fault or mains failure: Automatic emergency stop in case of fault or mains failure
P428
Automatic start
(Automatic start)
S
0 ... 1
{ 0 }
In the standard setting (P428 =0 Off) the inverter requires a flank to enable (signal change
from "low high") at the relevant digital input.
In the setting On 1 the FI reacts to a High level. This function is only possible if the FI is
controlled using the digital inputs. (see P509=0/1)
In certain cases, the FI must start up directly when the mains are switched on. For this P428 = 1
On can be set. If the enable signal is permanently switched on, or equipped with a cable
jumper, the FI starts up immediately.
NOTE:
(P428) not "ON" if (P506) = 6, Danger! (See note on (P506))
NOTE:
The "Automatic Start" function can only be used if a digital input of the frequency
inverter (DIN
1 … DIN 4) is parameterised to the function "Enable Right" or "Enable
Left" and this input is permanently set to "High". The digital inputs of the technology
units (e.g.:SK CU4 - IOE) do not support this "Automatic Start" function.
NOTE:
The "Automatic Start" function can only be activated if the frequency inverter has
been parameterised to local control ((P509) setting { 0 } or { 1} ).