6 Parameterisation
BU 0180 GB-0914
Pre-series version
87
6.1.3
Motor data / characteristic curve parameters
Parameter
{Factory setting}
Setting value / Description / Note
Device
Supervisor
Parameter
set
P200
Motor list
(Motor list)
P
0 ... 51
{ 0 }
Adjustment of the motor data from a list for 4-pole IE1 DS standard motors.
By selecting one of the possible digits and pressing the OK key, all motor parameters
(P201…P209) are adjusted to the selected standard power. The basis for the motor data is a
4-pole IE1 DS standard motor
0 = no change "No change to data"
1 = No motor: In this setting, the FI operates without current control, slip compensation and
pre-magnetising time, and is therefore not recommended for motor applications.
Possible applications are induction furnaces or other applications with coils and
transformers. The following motor data is set here:
50.0 Hz / 1500 rpm / 15.0 A / 400 V / 0.00 kW / cos
=0.90 / Star / R
S
0,01
/ I
EMPTY
6.5 A
2 = 0.12 kW 230 V
3 = 0.16 PS 230 V
4 = 0.18 KW 230 V
5 = 0.25 PS 230 V
6 = 0.25 kW 230 V
7 = 0.33 Hp 230 V
8 = 0.25 kW 400 V
9 = 0.33 Hp 460 V
10 = 0.37 kW 230 V
11 = 0.50 Hp 230 V
12 = 0.37 kW 400 V
13 = 0.50 Hp 460 V
14 = 0.55 kW 230 V
15 = 0.75 Hp 230 V
16 = 0.55 kW 400 V
17 = 0.75 Hp 460 V
18 = 0.75 kW 230 V
19 = 1.0 Hp 230 V
20 = 0.75 kW 400 V
21 = 1.0 Hp 460 V
22 = 1.1 kW 230 V
23 = 1.5 Hp 230 V
24 = 1.1 kW 400 V
25 = 1.5 Hp 460 V
26 = 1.5 kW 230 V
27 = 2.0 PS 230 V
28 = 1.5 kW 400 V
29 = 2.0 PS 460 V
30 = 2.2 kW 230 V
31 = 3.0 PS 230 V
32 = 2.2 kW 400 V
33 = 3.0 PS 460 V
34 = 3.0 kW 230 V
35 = 4.0 PS 230 V
36 = 3.0 kW 400 V
37 = 4.0 PS 460 V
38 = 4.0 kW 230 V
39 = 5.0 PS 230 V
40 = 4.0 kW 400 V
41 = 5.0 PS 460 V
42 = 5.5 kW 230 V
43 = 7.5 PS 230 V
44 = 5.5 kW 400 V
45 = 7.5 PS 460 V
46 = 7.5 kW 230 V
47 = 10 PS 230 V
48 = 7.5 kW 400 V
49 = 10.0 PS 460 V
50 = 11.0 kW 400 V
51 = 15.0 PS 460 V
NOTE:
As P200 returns to = 0 after the input confirmation, the control of the set motor can
be implemented via parameter P205.
P201
Nominal motor frequency
(Nominal motor frequency)
S
P
10.0 ... 399.9 Hz
{***}
The motor nominal frequency determines the V/f break point at which the FI supplies the
nominal voltage (P204) at the output.
P202
Nominal motor speed
(Nominal motor speed)
S
P
150 ... 24000 rpm
{***}
The nominal motor speed is important for the correct calculation and control of the motor slip
and the speed display (P001 = 1).
P203
Nominal motor current
(Nominal motor current)
S
P
0.1 ... 300.0 A
{***}
The nominal motor current is a decisive parameter for the current vector control.
*** These settings are dependent on the nominal power of the FI or the selection in parameter P200.