6 Parameterisation
BU 0180 GB-0914
Pre-series version
117
Parameter
{Factory setting}
Setting value / Description / Note
Device
Supervisor
Parameter
set
P528
Load monitoring Delay
(Load monitoring Delay)
S
P
0.10 ... 320.00 sec
{ 2.00 }
Parameter (P528) defines the delay time for which an error message ("E12.5") is suppressed on
infringement of the
defined monitoring range ((P525) … (P527)). A warning ("C12.5") is
triggered after half of this time has elapsed.
According to the selected monitoring mode (P529) an error message can also be generally
suppressed.
P529
Load monitoring mode
(Load monitoring mode)
S
P
0 ... 3
{ 0 }
The reaction of the frequency inverter to an infringement of the defined monitoring range
((P525) … (P527)) after the elapse of the delay time (P528) is specified by parameter (P529).
0 = Fault and warning, After the elapse of the time defined in (P528), an infringement of the
monitoring range produces a fault ("E12.5"). A warning ("C12.5") is given after the
elapse of half of this time.
1 = Warning, After the elapse of half of the time defined in (P528) and infringement of the
monitoring range produces a warning ("C12.5").
2 = Err. and warn. in const. "Fault and warning in constant travel", as for setting "0",
however monitoring is inactive during acceleration phases.
3 = Only warning
in
const., "Warning only during constant travel", as for setting
“1”,
however, monitoring is inactive during acceleration phases.