7 Status messages
BU 0180 GB-0914
Pre-series version
145
Display in the
SimpleBox
Fault
Text in the ParameterBox
Cause
Remedy
Group
Details in
P700[-01] /
P701
E012
12.0
External watchdog
The Watchdog function is selected at a digital input and the
impulse at the corresponding digital input is not present for
longer than the time set in parameter P460 >Watchdog
time<.
12.1
Motor limit
"Motor switch-off limit"
The drive switch-off limit (P534 [-01]) has triggered.
Reduce load on motor
Set higher value in (P534 [-01]).
12.2
Generator limit
"Generator switch-off limit"
The generator switch-off limit (P534 [-02]) has triggered.
Reduce load on motor
Set higher value in (P534 [-02]).
12.3
Torque limit
Limit from potentiometer or setpoint source has switched off.
P400 = 12
12.4
Current limit
Limit from potentiometer or setpoint source has switched off.
P400 = 14
12.5
Load limit
Switch-off due to overshooting or undershooting of
permissible load torques ((P525) … (P529)) for the time set
in (P528).
Adjust load.
Change limit values ((P525) ... (P527)).
Increase delay time (P528).
Change monitoring mode (P529).
12.8
Analog In minimum
Switch-off due to undershooting of the 0% adjustment value
(P402) with setting (P401) "0-10V with switch-off on error 1"
or "....2"
12.9
Analog In maximum
Switch-off due to overshooting of the 100% adjustment
value (P402) with setting (P401) "0-10V with switch-off on
error 1" or "....2"
E013
13.2
Shut-down monitoring
The slip error monitoring was triggered; the motor could not
follow the setpoint.
Check motor data P201-P209! This data is very important
for the current controller.
Check motor circuit.
Increase setting value for torque limit in P112.
Increase setting value for current limit in P536.
Check deceleration time P103 and extend if necessary
E014