3 Options
BU 0180 GB-0914
Pre-series version
59
3.3.4
Direction selection switch and potentiometer SK TIE4-SWT and SK TIE4-POT
The digital signals R and L of the direction selector switch SK TIE4-SWT (Part No.: 275274701) can be
applied directly to the corresponding digital inputs 1 and 2 of the frequency inverter.
The potentiometer (0-10 V) SK TIE4-POT (Part No.: 275274700) can be evaluated via the analog inputs of
the frequency inverter or the I/O extension. Each of the modules (control element) is supplied with a
pre-assembled cable. This must be plugged into the connection plug of the relevant module. The open ends
of the cable set must be wired to the terminal bar of the frequency inverter according to the table.
Both modules have protection class IP66.
Module
SK TIE4-SWT
Function
SK 1x0E
Color
FI
brown
24 V-supply voltage
43
Rotary switch
L - OFF - R
black
Enable R (e.g. DIN1)
21
white
Enable L (e.g. DIN2)
22
Module
SK TIE4-POT
white
Access to AIN +
14
Potentiometer
10kΩ
brown
Reference voltage 10 V
11
blue
Analog ground AGND
12
For examples of connections to the frequency inverter, please refer to Section 3.3.1.
Installation
Installation of the potentiometer (SK TIE4-POT) is possible on a 4 M25 versions of the device. In contrast,
installation of the switch (SK TIE-SWT) is only possible on the M25 holes 3BL and 3 BR; for Size 2 also
on 3AL: