7 Status messages

BU 0180 GB-0914

Pre-series version

137

Parameter

{Factory setting}

Setting value / Description / Note

Device

Supervisor

Parameter
set

P161

[-01]

...

[-09]

Filter time

(Filter time)

0 ... 400.00 ms

{ [-01] = 100 }

{ [-02] = 100 }

{ [-03] = 0 }

{ [-04] = 2 }

{ [-05] = 2 }

{ [-06] = 2 }

{ [-07] = 2 }

{ [-08] = 0 }

{ [-09] = 0 }

The analog and digital inputs are read cyclically every 250µs, this results in an input uncertainty
of 0.25ms. In order to eliminate bounce and smooth the input signals, the information which is
read in is passed through a filter routine. The filter time can be parameterised

If, for example, a filter time of 1 ms is parameterised for a digital input, the input signal is
delayed by approx. 1...1.25ms.

The parameterisation of the filter time for the analog outputs is used to round off signal jumps.

[-01] = AIN1

[-02] = AIN2

[-03] = AOUT

[-04] = DIN1

[-05] = DIN2

[-06] = DIN3 (SK TU4-IOE only)

[-07] = DIN4 (SK TU4-IOE only)

[-08] = DOUT1 (SK TU4-IOE only)

[-09] = DOUT2 (SK TU4-IOE only)

P162

Send broadcast

(Send broadcast)

0 ... 1

{ 0 }

Activation of this parameter (setting On 1 ) switches the I/O extension module into broadcast
mode and thus enables simultaneous access by up to four frequency inverters. Each frequency
inverter evaluates the information from the I/O extension individually.

The addressing of the module (DIP switches) is no longer taken into account.

0 = Off

1 = To:

NOTE:

The received data are linked in the I/O module using OR logic. If several frequency
inverters are linked to the digital outputs of the module, the relevant output is set to
"High" as soon as an inverter accesses it. The analog outputs behave in a similar
manner. Here, the highest value has priority.

P163

AOut Inverse

(Invert analog output)

0 ... 1

{ 0 }

The function of the analog output can be inverted

0 = No inversion

1 = Analog output signal is inverted