3 electrical data 3~400v – NORD Drivesystems BU0180 User Manual

Page 156

background image

SK 180E Manual for frequency inverters

156

Pre-series version

BU 0180 GB-0914

8.2.3

Electrical data 3~400 V

Size 1

Device type:

SK 1x0E… -250-340-B

-370-340-B

-550-340-B

-750-340-B

-111-340-B

Nominal motor power

(4-pole standard motor)

400 V

0.25 kW

0.37 KW

0.55 kW

0.75 kW

1.1 kW

480 V

1

/

3

hp

½ hp

¾ hp

1 hp

1½ hp

In

p

u

t

Mains voltage

3~ 400 V

3 AC 380 ... 480V, -20% / +10%, 47 ... 63 Hz

Typical input
current at 400V

3~ rms

2.0 A

2.3 A

2.6 A

3.2 A

4.1 A

3~ FLA

1.7 A

1.9 A

2.2 A

2.7 A

3.5 A

Rec. mains fuse

1 AC

slow-acting [A]

10 A

10 A

10 A

10 A

10 A

Permissible mains
fuses (UL)

RK5 or faster

fuses,

min 230V/400 V

5.0 A

5.0 A

5.0 A

5.0 A

10 A

Bussmann

FRS-R-5

FRS-R-5

FRS-R-5

FRS-R-5

FRS-R-10

Circuit breaker*

min. 230V/400 V

5.0 A

5.0 A

5.0 A

5.0 A

10 A

O

u

tp

u

t

Output voltage

3~ 400 V

3 AC 0 - Mains voltage

Nominal output
current at 400V

rms

1.2 A

1.5 A

1.7 A

2.3 A

3.1 A

Motor Assembly**

1.1 A

1.3 A

1.5 A

2.1 A

2.8 A

Wall-mounted**

1.1 A

1.3 A

1.5 A

2.1 A

2.8 A

Motor mounting (ventilation with motor fan)

Max. continuous power / max. continuous current:

S1-50°C

S1-40°C

0.25 kW / 1.2

A

0.25 kW / 1.2

A

0.37 kW / 1.5 A

0.37 kW / 1.5 A

0.55 kW / 1.7

A

0.55 kW / 1.7

A

0.75 kW / 2.3

A

0.75 kW / 2.3

A

0.75 kW / 2.3 A

1.10 kW / 3.1 A

Max. permissible ambient temp. with nominal output current

S1

S3

70%ED 10min

S6

70%ED 10min (100% / 20%Mn)

50°C

50°C

50°C

50°C

50°C

50°C

50°C

50°C

50°C

50°C

50°C

50°C

40°C

50°C

50°C

Wall mounting (unventilated)

Max. continuous power / max. continuous current:

S1-50°C

S1-40°C

0.25 kW / 1.2 A

0.25 kW / 1.2 A

0.37 kW / 1.5 A

0.37 kW / 1.5 A

0.55 kW / 1.7 A

0.55 kW / 1.7 A

0.75 kW / 2.0 A

0.75 kW / 2.3 A

0.75 kW / 2.0 A

1.10 kW / 2.6 A

Max. permissible ambient temp. with nominal output current

S1

S3

70%ED 10min

S6

70%ED 10min (100% / 20%Mn)

50°C

50°C

50°C

50°C

50°C

50°C

50°C

50°C

50°C

40°C

50°C

50°C

30°C

40°C

40°C

* Circuit Breaker (inverse time trip type) as per UL489

** FLA (S1-40 °C)