1 operating displays – NORD Drivesystems BU0180 User Manual

Page 79

background image

6 Parameterisation

BU 0180 GB-0914

Pre-series version

79

6.1.1

Operating displays

The abbreviations used are described in Section 9.12

“Abbreviations in this Manual".

Parameter

{Factory setting}

Setting value / Description / Note

Device

Supervisor

Parameter
set

P000

Operating para. disp.

(Operating parameter display)

0.01 ... 9999

In the SimpleBox (SK CSX-3H) display, the parameter value online selected in P100 is
displayed.

P001

Selection display

(Selection display)

0 ... 65

{ 0 }

0 = Actual frequency [Hz], is the actual output frequency being supplied by the FI.

1 = Speed [rpm], the actual speed calculated by the FI.

2 = Setpoint frequency [Hz], the output frequency equivalent to the actual setpoint. This

need not match the actual output frequency.

3 = Current [A], the actual output current measured by the FI.

4 = Torque current [A], the torque developing output current of the FI.

5 = Voltage [V AC], the actual alternating voltage being output by the FI.

6 = Link voltage [V DC], "link voltage" is the internal DC voltage of the FI. Amongst other

things, this depends on the level of the mains voltage.

7 = cos Phi, the currently calculated value of the power factor.

8 = Apparent power [kVA], the actual apparent power calculated by the FI.

9 = Effective power [kW], the actual effective power calculated by the FI.

10 = Torque [%], the actual torque calculated by the FI.

11 = Field [%], the actual field in the motor calculated by the FI.

12 = Operating hours [h]: time that voltage is applied to the FI network.

13 = Operating time Enable [h], "Enable operating hours" is the time for which the FI is

enabled.

14 = Analog input 1 [%], actual value AIN1 of the first I/O extension SK xU4-IOE.

15 = Analog input 2 [%], actual value AIN2 of the second I/O extension SK xU4-IOE.

16 =

… 18 reserved

19 = Heat sink temperature [°C]: current temperature of the FI heat sink.

20 = Motor load [%]: average motor load, based on the known motor data (P201...P209).

21 = Brake resistor load - R [%], "Brake resistor load" average brake resistor load, based on

the known resistance data (P556...P557).

22 = Internal temperature [°C], current temperature in FI housing.

23 = Motor temperature [°C], only in combination with the analog input and appropriate

wiring (KTY84).

30 = Actual motor potentiometer setpoint [Hz], advance display of the setpoint (without the

drive unit running) can be set via the motor potentiometer function 71 / 72 (see
parameter P420).

50 =

… 54 reserved

60 = R Stator Ident: stator resistance, automatic determination of motor data, P220

61 = R Rotor Ident: rotor resistance, automatic determination of motor data, P220

62 = L Leakage Stator Ident, stator leakage inductance, from automatic determination of

motor data, P220

63 = L Stator Ident: stator inductance, from automatic determination of motor data, P220

64 = Reserved

65 = Reserved