2 basic parameter (frequency inverter) – NORD Drivesystems BU0180 User Manual
Page 80
SK 180E Manual for frequency inverters
80
Pre-series version
BU 0180 GB-0914
Parameter
{Factory setting}
Setting value / Description / Note
Device
Supervisor
Parameter
set
P002
Display factor
(Display factor)
S
0.01 ... 999.99
{ 1.00 }
The selected operating value in parameter P001 >Select of display< is multiplied with the
scaling factor in P000 and displayed in >Operating parameter display<.
It is therefore possible to display system-specific operating such as e.g. the throughput quantity
P003
Supervisor code
(Supervisor code)
0 ... 9999
{ 1 }
0 = The Supervisor parameters are not visible. Otherwise, all parameters are visible.
1 = All parameters are visible.
2 = ... 9999, (except 65) only parameters P001 and P003 are visible.
6.1.2
Basic parameter (frequency inverter)
Parameter
{Factory setting}
Setting value / Description / Note
Device
Supervisor
Parameter
set
P100
Parameter set
(Parameter set)
S
0 ... 3
{ 0 }
Selection of the parameters sets to be parameterised. 4 parameter sets are available. All
parameter set-dependent parameters are identified by P.
The selection of the operating parameter set is performed via a digital input or the Bus control.
Switching can take place during operation (online).
Setting
Digital input
function [8]
Digital input
function [17]
LEDs
SimpleBox
0 = Parameter set 1
Low
Low
1
2
1 = Parameter set 2
High
Low
2
1
2 = Parameter set 3
Low
High
1
2
3 = Parameter set 4
High
High
2
1
If enabled via the keyboard (SimpleBox, PotentiometerBox or ParameterBox), the operating
parameter set will match the settings in P100.