beautypg.com

4 overvoltage filter sk cif – NORD Drivesystems BU0180 User Manual

Page 28

background image

SK 180E Manual for frequency inverters

28

Pre-series version

BU 0180 GB-0914

2.4 Overvoltage filter SK CIF

The use of a suitable ("CSA-") overvoltage filter is mandatory (see also Section 1.5) in order to comply with
cUL requirements. For 230V devices, operation of the frequency inverter with a suitable overvoltage filter is
only permissible if a mains choke is used in addition.

For further information about the overvoltage filter, please refer to the relevant data sheet. These data
sheets can be downloaded at

www.nord.com

.

Inverter ID

Filter type

Data sheet

SK 1x0E-250-323-A

SK 1x0E-111-323-A*

SK CIF-323-20

(alternatively SK CIF-323-40)

TI 030 276997070

(TI 030 276997071)

SK 1x0E-250-340-A

SK 1x0E-221-340-A

SK CIF-340-30

(alternatively SK CIF-340-60)

TI 030 276997080

(TI 030 276997081)

* (only with suitable mains choke)

Without an overvoltage filter, frequency inverters for 1~ 115V mains (SK1x0E-xxx-112-O) cannot be
approved according to cUL.

CAUTION!

Modules SK CIF-323-x0 may only be used in combination with a suitable mains choke
(L

min

= 3 x 0,73 mH) (see connection diagram).

For SK CIF-340-x0 modules the use of a mains input choke is not mandatory, but is recommended.

Note

With the use of a mains choke, the effective input currents of the 1~ 230V frequency inverter reduce
to approximately the values of the output currents. Several frequency inverters can be connected to
a choke - filter combination. In this case, the total input currents must not exceed the current rating
of the filter.