7 Status messages

BU 0180 GB-0914

Pre-series version

139

Parameter

Setting value / Description / Note

Device

Supervisor

Parameter
set

P173

Module status

(Status of the module)

0 ... FFFF (hex)

Possible displayed values:

Bit 0 = not used
Bit 1 = not used
Bit 2 = not used
Bit 3 = not used
Bit 4 = not used
Bit 5 = not used
Bit 6 = System bus “BUS WARNING”
Bit 7 = System bus “BUS OFF”
Bit 8 = Status FI1 (Low - Bit)
Bit 9 = Status FI1 (High - Bit)
Bit 10= Status FI2 (Low - Bit)
Bit 11= Status FI2 (High - Bit)
Bit 12= Status FI3 (Low - Bit)
Bit 13= Status FI3 (High - Bit)
Bit 14= Status FI4 (Low - Bit)
Bit 15= Status FI4 (High - Bit)

Status for FI x:

BIT High

BIT Low

Meaning

0

0

FI is offline

0

1

Unknown FI

1

0

FI is online

1

1

FI lost (switched off)

P174

State of digital in.

(Status of digital inputs)

0 ... 15

Instantaneous image of input level logic of the digital inputs.

Possible displayed values:

Bit 0= Input 1 ((DIN1) (of the BUS module))
Bit 1= Input 2 ((DIN2) (of the BUS module))
Bit 2= Input 3 ((DIN3) (of the BUS module))
Bit 3= Input 4 ((DIN4) (of the BUS module))

P175

Relay status

(State of relays)

SK TU4-IOE

0 ... 3

Instantaneous image of output level logic of the digital output.

Possible displayed values:

Bit 1= Output 1 ((DO1) (of the BUS module))
Bit 2= Output 2 ((DO2) (of the BUS module))

P176

... [-01]

...

... [-03]

Actual voltage

(Actual voltage)

0.0 ... 10.0 V

Displays the voltage level of the signals at the analog inputs/outputs of the I/O extension
module.

… [-01] = Current voltage (AIN1)

… [-02] = Current voltage (AIN2)

… [-03] = Current voltage (AOUT)